Daikin EUWY095BZ6Y [47/52] Installation

Daikin EUWY095BZ6Y [47/52] Installation
1
10
Applied Systems • Chillers
49
Chillers • R-407C • EUWY-BZ6Y
10 Installation
10 - 1 Installation method
Dimensions of recommended slings and swing-bar: EUWY*
030 035 040 045 049 050 060 070 080 090 095
Without buffer tank
A (mm) 1400 1400 1400 1400 1400 2400 2400 2400 2400 2400 2400
B (mm) 2300 2300 2500 2500 2500 3100 3100 3100 3100 3100 3100
With buffer tank
A (mm) 1400 1400 1400 1400 1400 2400 2400 2400 2400 2400 2400
B (mm) 2700 2800 3100 3100 3100 3400 3400 3400 3400 3400 3400
Shipping weights EUWY*
030 035 040 045 049 050 060 070 080 090 095
Without hydraulic module
EUWY (kg) 864 996 1136 1272 1296 1650 1860 2114 2271 2434 2467
Additional weight for single pump hydraulic module
EUWY (kg) 29 34 34 64 64 66 66 70 70 84 84
Additional weight for dual pump hydraulic module
EUWY (kg) 103 108 108 108 108 110 110 114 114 189 189
Additional weight for buffer tank
EUWY (kg) 396 437 436 436 436 644 644 644 644 644 644