Daikin EWLDС13I-SS Брошюра онлайн [15/36] 529438

Daikin EWLD900I-SS Брошюра онлайн [15/36] 529433
15
ELECTRICAL SPECIFICATIONS 320 400 420 500
--- 3 3 3 3
Hz 50 50 50 50
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A 330 464 464 464
A 135 164 188 216
A 195 242 282 321
A 215 266 310 353
No.3333
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A 195 242 282 321
---
ELECTRICAL SPECIFICATIONS 600 650 750 800
--- 3 3 3 3
Hz 50 50 50 50
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A 486 620 658 690
A 268 296 325 350
A 390 437 484 524
A 429 481 532 576
No.3333
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A
195
195
195
242
242
242
242
282
---
ELECTRICAL SPECIFICATIONS 850 900 950 C10
--- 3 3 3 3
Hz 50 50 50 50
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A 690 721 721 814
A 375 407 437 457
A 564 603 642 679
A 620 663 706 747
No.3333
V 400 400 400 400
Minimum % -10% -10% -10% -10%
Maximum % +10% +10% +10% +10%
A
282
282
282
321
321
321
195
242
242
---
EWLD~I-SS
Maximum running current
Maximum current for wires sizing
Voltage
Voltage Tolerance
Power Supply
Phase
Frequency
Voltage Tolerance
Maximum running current
Unit
Maximum starting current
Nominal running current cooling
Wye – Delta type (Y – Δ)
EWLD~I-SS
Compressor
Phase
Voltage
Voltage
Voltage Tolerance
Starting method
Maximum running current
Maximum current for wires sizing
Power Supply
Phase
Frequency
Voltage Tolerance
Maximum running current
Unit
Maximum starting current
Nominal running current cooling
Wye – Delta type (Y – Δ)
EWLD~I-SS
Compressor
Phase
Voltage
Voltage Tolerance
Starting method
Maximum current for wires sizing
Power Supply
Phase
Frequency
Voltage
Maximum running current
Unit
Maximum starting current
Nominal running current cooling
Maximum running current
Compressor
Phase
Voltage
Voltage Tolerance
Starting method Wye – Delta type (Y – Δ)
Notes
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of compressors at 75% maximum load
Maximum unit current for wires sizing is based on minimum allowed voltage
Nominal current in cooling mode is referred to the following conditions: evaporator 12°C/7°C;
saturated discahrge temperature 45°C
Maximum running current is based on max compressor absorbed current in its envelope
Maximum current for wires sizing: (compressors full load ampere) x 1,1.