Daikin EWLDС13I-SS [18/36] Operating limits

Daikin EWLD850I-SS [18/36] Operating limits
18
Operating limits
EWLD~I-SS
Table 1 - Evaporator minimum and maximum water Δ
t
Max evaporator water ΔC8
Min evaporator water ΔC4
Table 2 - Evaporator fouling factors
Table 3.1 - Minimum glycol percentage for low water temperature
2 0 -2 -4 -6 -8
10 20 20 20 30 30
10 20 20 30 30 30
Note: Minimum glycol percentage to be used with evaporator leaving water temperature below 4°C to prevent freezing of water circuit.
Table 3.2 - Minimum glycol percentage for low air temperature
-3 -8 -15 -23 -35
10% 20% 30% 40% 50%
-3 -7 -12 -20 -32
10% 20% 30% 40% 50%
Note (1): Minimum glycol percentage to prevent freezing of water circuit at indicated air ambient temperature
Propylene glycol (%) (1)
Note (2): Air ambient temperature do exceed the operating limits of the unit, as protection of water circuit may be needed in winter season at
non-working conditions
Air Ambient Temperature (°C) (2)
Air Ambient Temperature (°C) (2)
Ethylene glycol (%) (1)
Ethylene glycol (%)
Propylene glycol (%)
Evaporator Leaving Water Temperature (°C)
1.000
0.992
0.983
0.975
0.986
0.974
0.962
0.0176
0.0440
0.0880
0.1320
1.000
0.978
0.957
0.938
1.000
Fouling factors
m
2
°C / kW
Cooling capacity
correction factor
Power input
correction factor
EER
correction factor
20
25
30
35
40
45
50
55
60
65
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
EvaporatorLeavingWaterTemp.C)
CondenserLeavingWaterTemp.C)
OperationwithGlycol
(below4°CEvapLWT)