EXTECH MG320 [6/12] Insulation resistance measurements

EXTECH MG320 [6/12] Insulation resistance measurements
6 MG310-en-GB_V1.0 12/15
INSULATIONRESISTANCEMEASUREMENTS
1. Selectthedesiredtestvoltageusingtherotaryfunctionswitch.Selectthe250V,500V,or
1000Vswitchpositionforthecorrespondingoutputtestvoltage.
2. Connecttheredtestleadtothemeter’sLINE(4)jackandtheblacktestleadtotheEARTH
(1)jack.Connectthe
probeendofthetestleadstothecircuitundertest.
3. PresstheTESTbuttontotest.The
buttonwillselflockandthebutton
lampwilllight.
Note:Ifthecircuitundertestislive
andhasavoltagepotential(AC/DC)
over30V,themeterwillnottest
(the
displaywillshowthe“>”iconand
the
symbolwillflash;thebuzzer
willalsosound).Ifthecircuitunder
testisnotliveorifitsvoltageisless
than30V,themeterwillbegin
applyinghighvoltagetothecircuit
undertest.
4. Theprimarydisplaywillshowthe
insulationresistanceinMΩ
(megaohms)orGΩ
(gigaohms).
5. Thetestvoltage(VDC)valuewillbe
indicatedintherightmostauxiliary
display,the
symbolwillflashandthecautionbuzzerwillsound.
6. PresstoreleasetheTESTbuttontostopthe test.Thehighvoltagewillswitchoffandthe
resistancevalueindicatedintheprimarydisplaywillhold.
7. Subsequently,themeterwillinternallydischargethebalanceoftheinsulationtestvoltage.
Note:Turningthefunctionswitchtoanothertestpositionwillabortthetest.
8. Areadingof>5.50Gindicatesthatthemeterreadingisabovetheresistancethresholdof
thatmeasurementrange.
CAUTION
Beforetakingmeasurementsdisconnecttheunitundertestfromallpowersourcesandisolateit
fromanystrayresistance.
Donotshortcircuitthetestleadswhenvoltageisoutputfromthemeter.
Allowsufficienttimebetweentestsfordevicesundertesttostabilize.
Whenredand
blackclipsareconnectedtothecircuitundertest,highvoltageisoutputfromthe
LINEjackandcurrentfromtheEARTHjack.
Atthecompletionofatest,donottouchanypartsofthecircuitundertest.Componentsmayhave
becomechargedduringthetestandcould
dischargewhentouched.
Скачать