Operation
Powering the meter
Press the ON button to turn the unit on. Press the OFF button to turn the unit off. If the meter
does not switch ON please check that fresh ‘C’ 1.5V alkaline batteries are installed in the battery
compartment located at the bottom of the instrument.
Insulation Resistance Testing Procedure
Warning: The circuit under test must be completely de-energized and isolated before making
test connections.
1. After turning the unit on, make sure that the Replace Battery message is not displayed. If
the Replace Battery message is displayed replace the batteries before proceeding.
2. The test voltage defaults to 2500V on power up. Select the desired test voltage using the
Voltage Adjust buttons (±500V) that step through the available test voltages in 500V
increments or by pressing one of the preset test voltage buttons (10kV, 5kV, 2.5kV, 1Kv).
3. The display shows the Connect Leads prompt along with the selected test voltage value.
Connect the Green test lead to the Green test socket on the meter and then to the Ground
side of the insulator under test.
Connect the Red lead to the Red test socket on the meter and the Blue guard cable to the
blue socket on the meter. Connect the service end of the Red cable to other side of the
insulator under test.
If a Leakage Guard lead is required to collect surface leakage, connect the separate Blue test
lead into the Blue guard lead from the Red test lead which is plugged into the Blue test
socket on the meter and then clip the service end of the cable to the surface of the insulator
under test.
4. Momentarily Press the TEST START/STOP button (1.5s
〜3 seconds) to start testing.
For DAR or PI testing – refer to the separate test procedure below.
5. The Insulation resistance test will complete in 5 seconds. The test voltage percentage
steadily counts down to zero during the test as can be seen on the display. The resistance
test result value will appear on the display when the test has completed.
6. The HOLD icon will appear in place of the bargraph when the test is complete and after the
voltage has been discharged.
WARNING: DO NOT REMOVE THE TEST LEADS BEFORE THE HOLD DISPLAY APPEARS.
7. The meter automatically discharges the system at the end of the test.
8. To take another test, press the TEST START/STOP button, the Connect Leads prompt should
appear on the display; the instrument is now ready to run a new test.
9. The instrument automatically powers down after 5 minutes of inactivity.
Содержание
- Kv digital high voltage insulation tester 1
- Model mg500 1
- User manual 1
- International safety symbols 2
- Introduction 2
- Safety 2
- Features 4
- Description 5
- Connecting the test leads to the device under test 6
- Connecting the test leads to the meter 6
- Meter preparation 6
- Insulation resistance testing procedure 7
- Operation 7
- Powering the meter 7
- Dar and pi tests dar dielectric absorption ratio and pi polarization index 8
- The enersav 8
- Automatic discharge 9
- Automatic test stop 9
- Automatic under over range resistance detect 9
- Bargraph voltage display 9
- Elapsed timer 9
- Live circuit warning 9
- Manual test stop 9
- Ac motor test 10
- Application specific information 10
- Measuring power tools and small appliances 10
- Dc motor test 11
- Testing multi conductor cables 11
- Testing single conductor cables 11
- Notes on measuring the resistance of a contactor or circuit breaker 12
- Transformer testing 12
- Unusual insulation resistance measurement applications 12
- Dirty insulator 13
- Electrical equivalent circuit dirty insulator typical test 13
- Insulator measurement considerations 13
- Battery replacement 14
- Cleaning 14
- Maintenance 14
- Complies with 15
- Copyright 2013 2017 flir systems inc 15
- Specifications 15
- Www extech com 15
Похожие устройства
- EXTECH MG500 Data Sheet
- EXTECH MG500 Инструкция язык en
- Fluke FLK-1503 Инструкция по эксплуатации
- Fluke FLK-1503 Инструкция язык en
- Fluke FLK-1503 Data Sheet
- Fluke FLK-1503 Расширенная инструкция
- Fluke FLK-1507 Инструкция по эксплуатации
- Fluke FLK-1507 Data Sheet
- Fluke FLK-1507 Инструкция язык en
- Fluke FLK-1507 Расширенная инструкция
- Fluke FLK-1550C Инструкция по эксплуатации
- Fluke FLK-1550C Инструкция язык en
- Fluke FLK-1550C Data Sheet
- Fluke FLK-1550C Расширенная инструкция
- Fluke FLK-1550C-KIT Инструкция по эксплуатации
- Fluke FLK-1550C-KIT Инструкция язык en
- Fluke FLK-1550C-KIT Расширенная инструкция
- Fluke FLK-1550C-KIT Data Sheet
- Fluke FLK-1550CFC-KIT/IR Инструкция по эксплуатации
- Fluke FLK-1550CFC-KIT/IR Инструкция язык en