MEAN WELL RCP-1000-48-C [5/8] Series

MEAN WELL RCP-1UT [5/8] Series
Derating Curve
CN500 Pin No. Assignment
CN500 IN/OUT Connector pins function description
Static Characteristics
INPUT VOLTAGE (VAC) 60Hz
90 95 100 115 264
90
100
80
70
60
50
40
AMBIENT TEMPERATURE ( )
20
40
60
80
100
-20 0 10 20 30 40 50 60 70
RCP
seri e s
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No. Pin No. Pin No. Pin No. Pin No.
2
1
3
4
5
Assignment Assignment Assignment Assignment Assignment
AC-OK-A
ON/OFF-A
DC-OK-A
V-TRIM-A
T-ALARM-A
7
13
9
8
10
14
15
6
12
11 16
17
23
21
22
25
18
19
20
24
AC-OK-B
DC-OK-B
ON/OFF-B
+5V-AUX
GND-AUX
NC
CS
ON/OFF-C
V-TRIM-B
T-ALARM-B
AC-OK-C
DC-OK-C
SCL
-S
+V
-V
V-TRIM-C
T-ALARM-C
+S
SDA
Pin No. Function
Description
1,8,15
2,9,16
3,10,17
4,11,18
5,12,19
7
23
25
14
6
ON/OFF
AC-OK
DC-OK
V-TRIM
T-ALARM
GND-AUX
SCL
-V
CS
+5V-AUX
Each unit can separately turn the output on and off by electrical or dry contact between ON/OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
Low : When the input voltage is 82Vrms +/-4V. High : when the input voltage in 82Vrms +/-4V.
High : When the Vout 80%+/-5%. Low : When Vout 80%+/-5%
Connection for output voltage trimming. The voltage can be trimmed within its defined range.
High : When the internal temperature is within safe limit. Low : 10 below the thermal shut down limit.
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Serial clock used in the I C interface option. Refer to the I C interface description.
Negative output voltage. For local sense use only, can't be connected directly to the load.
Current sharing signal. When units are connected in parallel, the CS pins of the units should be connected to allow current balance
between units.
Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7). The maximum load current is 0.3A. This output has the built-in
"Oring diodes" and is not controlled by the remote ON/OFF control.
2 2
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
20
21
+S
-S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
22 +V
Positive output voltage. For local sense use only, can't be connected directly to the load.
24 SDA
Serial data used in the I C interface option. Refer to the I C interface description.
2 2