Daikin EWAT310B-SRA2 [4/62] Features and benefits

Daikin EWAT290B-SRA1 [4/62] Features and benefits
FEATURES AND BENEFITS
4/62
Compressors
Hermetic orbiting scroll type optimized for R-32 operation and complete with motor over-temperature and
over-current protection devices. Each compressor is equipped with an oil heater that keeps the oil from being
diluted by the refrigerant when the chiller is not running. The compressors are connected in Tandem or Trio
configuration on each refrigerant circuit. Each compressor is mounted on rubber antivibration mounts for a
quite operation. Unit is delivered with complete oil charge.
Evaporator
The unit is equipped with a direct expansion plate-to-plate type evaporator optimized for R-32 refrigerant
operation. This heat exchanger is made of stainless steel brazed plates and is covered with 10mm closed cell
insulation material. The exchanger is equipped with an electric heater for protection against freezing and
evaporator water connections are provided with victaulic kit (as standard). The evaporator is manufactured
in accordance to 2014/68/EU. The evaporator flow switch and the evaporator water filter are available as
option (shipped loose). Note the installation of an evaporator flow switch and an evaporator water filter is
mandatory.
Condenser
The condenser is made entirely of aluminum and it is optimized for R-32 refrigerant operation. Full-depth
louvered aluminum fins are inserted between the aluminum tubes maximizing the heat exchange.
The Microchannel technology ensures the highest performance with the minimum surface for the exchanger.
This technology reduces unit refrigerant charge compared to traditional copper tubes and aluminum
condenser.
Special treatment ensure resistance to the corrosion by atmospheric agents extending the lifetime.
Note: applications in industrial, costal, highly polluted urban environment or combinations of them, require
proper evaluation to understand if additional measures are needed to protect the condenser coil from the
aggressive environment.
Condenser fans
Condenser fans are propeller type with high efficiency design blades to maximize performances. The blades
are made of glass-reinforced resin and a guard protects each fan.
Single-V units are equipped as standard with fan speed modulation (phase cut).
Multi-V units (standard and low sound versions) are equipped with on/off fans and inverter drive is available
as an option. Multi-V units reduced noise versions are equipped with inverter driven fans as standard.
Electronic expansion valve
The unit is equipped with electronic expansion valves to achieve precise control of R-32 refrigerant mass flow.
As today’s systems require improved energy efficiency, accurate temperature control, wide range of operating
conditions, the application of electronic expansion valves becomes mandatory.
Electronic expansion valves has unique features: short opening and closing time, high resolution, positive
shut-off function to eliminate use of additional solenoid valve, continuous modulation of mass flow without
stress in the refrigerant circuit and corrosion resistance stainless steel body.
If compared to traditional thermostatic valves, electronic expansion valves allow the system to work with low
condenser pressure (winter time) without any refrigerant flow problems and the perfect control of the chilled
water temperature.
Refrigerant circuit
Each unit has one or two independent refrigerant circuits and each one includes:
Compressor
Refrigerant
Evaporator
Air Cooled Condenser
Electronic expansion valve
Sight glass with moisture indicator
Filter drier
Charging valves
High pressure switch
High pressure transducers
Low pressure transducers
Oil pressure transducer
Suction temperature sensor
Electrical panel
Power and control are in the main panel that is manufactured to ensure protection against all weather
conditions. The electrical panel is IP54 and (when opening the doors) internally protected against possible

Содержание