INSTALLATIONS NOTES
TECHNICAL SPECIFICATIONS
Controller features
Controller shall be guarantee following minimum functions:
Management of the compressors.
Chiller enabled to work in partial failure condition.
Full routine operation at condition of:
-
high ambient temperature value
-
high thermal load
-
high evaporator entering water temperature (start-up)
Display of evaporator entering/leaving water temperature.
Display of Outdoor Ambient Temperature.
Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each
circuit.
Leaving water evaporator temperature regulation.
Compressor and evaporator pumps hours counter.
Display of Status Safety Devices.
Number of starts and compressor working hours.
Optimized management of unit load.
Fan management according to condensing pressure.
Re-start in case of power failure (automatic / manual).
Soft Load (optimized management of the unit load during the start-up).
Start at high evaporator water temperature.
Return Reset (Set Point Reset based on return water temperature).
OAT (Outside Ambient temperature) set-point reset.
Set point Reset from external signal (optional).
Application and system upgrade with commercial SD cards.
Ethernet port for remote or local servicing using standard web browsers.
Master / Slave (provided as standard)
Variable primary Flow (available as option)
Two different sets of default parameters could be stored for easy restore.
High Level Communications Interface (on request)
The chiller shall be able to communicate to BMS (Building Management System) based on the most common
protocols as:
-
ModbusRTU
-
LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology
-
BacNet BTP certified over IP