Daikin EWAD740C-SS [215/304] Entering evaporator water temperature sensor fault

Daikin EWADC14C-XL [215/304] Entering evaporator water temperature sensor fault
ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–15
33
4
5
1
1.3.1 Entering Evaporator Water Temperature Sensor Fault
Event description (as shown on screen): EWT Sensor Fail.
Trigger: Sensor shorted or open.
Action Taken: Return water reset cannot be used.
Reset: Auto reset when sensor is back in range.