1.5.3 High Condenser Pressure - Hold
Event description (as shown on screen): CondPressHigh Hold N.
Trigger: While the compressor is running and unit mode is Cool, if saturated condenser temperature
is higher or equal to the High Saturated Condenser Hold Value, the event is triggered.
Action Taken: Inhibit loading.
Reset: While still running, the event will be reset if saturated condenser temperature drops below the
High Saturated Condenser Hold Value - 5°C. The event is also reset if the unit mode is switched to
Ice, or the circuit is no longer in the run state.