Daikin UAT180CGXY1 [9/16] English

Daikin UAT240CGXY1 [9/16] English
7
PHYSICAL DATA
ELECTRICAL DATA
WIRE CONNECTION
English
Description
Model
UAT150C UAT180C UAT240C UAT300C
Power supply V/Ph/Hz
380-415/3N~/50
Max continuous current (Comp) A
20.0/20.0 24.2/24.2 31.0/31.0 42.0/35.0
Full load current (FLA, Comp) A
13.7/13.7 16.8/16.8 22.3/22.3 31.0/25.0
Locked rotor current (LRA, Comp) A
100.0/100.0 111.0/111.0 118.0/118.0 174.0/140.0
*Min. circuit amps, MCA A
48.0 57.0 72.5 85.0
*Max. fuse amps, MFA A
63.0 63.0 80.0 100.0
PE
a
b
c
d
g
e
f
All electrical work must be carried out by qualified electrician and accordance with local supply requirement and associate
regulation.
Before connecting the wire, consult the electric power company of jurisdiction.
(2) Wi i i i
a. Power supply d. Unit
b. Main switch/fuse
( eld supply)
e. Remote control/Thermostat
f. Connection wiring for
unit & remote controllerc. Power supply
wiring for unit
g. Earth
(1) The entire wiring diagram of unit
Description
Model
UAT150C UAT180C UAT240C UAT300C
Refrigerant R22
Refrigerant charge kg 4.6/4.6 6.0/6.0 8.0/8.0 10.6/10.6
Evaporator air flow
CFM 4600 6500 7900 8700
L/S 2171 3068 3728 4106
External static pressure
mmAq 12.5 15 20 25
Pa 123 147 196 245
Condenser air flow
CFM 9900 13800 12230 21500
L/S 4672 6513 5772 10149
Control Mechanical Controller/Sequential Controller
Compressor (Type/Quantity) Scroll/2
Air filter (Type/Quantity) Washable Saranet/2
Air filter dimension (L x W x T) mm 895 x 685 x 4 834 x 760 x 4 1040 x 750 x 4
1 IM RTC-0712(0)-DAIKIN-EN.indd 71 IM RTC-0712(0)-DAIKIN-EN.indd 7 8/10/12 11:25:58 AM8/10/12 11:25:58 AM