Daikin UATC10AMY1 [32/43] Wiring diagram

Daikin UATC10AMY1 [32/43] Wiring diagram
3
1
10
Rooftops • Cooling only
28
Cooling only • R-22 • UAT-AMY1
10 Wiring diagram
10 - 1 Wiring diagram
UAT240/280/320AY1
Caution,
1.To protect each Fan motor and compressor from abnormal current, Over current relays <51C>, <51F> are installed. Therefore, do not change
factory set value of Over current relays.
N
OTES
1 The dotted lines show field wiring.
2 The figure in the parenthesis shows field supply parts.
3 Color of earth is yellow and green twisting.
CN2
COMP.
L
N
L1
RED
C11
(3.15A)
F1
3
2
1
N
PE
TB1
52C1
51F1
52F
MF1
TB2
N
L3
L1
L2
52C
52F
26L
47
1
10
3
51F
52C
CH
63H
2
MC
51C
11
MF2
X1
47
X1
51C
TB1
PCB
52C
47
A
C
F G
51C
52F1
D
51F1
R
X1
Power Supply
380~415VAC
3N~PE
50Hz
SLM
REMOTE
CONTROL
TRANSFORMER
BLACK
INTERNAL
PROTECTOR
SYMBOL NAME
MC Compressor motor
MF1 Fan motor (indoor)
MF2 Fan motor (outdoor)
52C Contactor (Compressor)
52F1 Contactor (fan I/D)
51C Over current relay (comp)
TB1 Terminal block
F1 Fuse 3.15A
51F Over current relay (fan I/D)
63H High-pressure switch
CH Crankcase heater
26L Sensor (freeze protection)
PCB Printed circuit board
47 Phase Protector / Discharge thermostat
X1 Auxiliary Relay (Self hold)
49F Internal protector (OD fan) FOR UAT240/280AY1 ONLY
BLACK
RED
RED
WHITE
WHITE
BLACK
WHITE
RETURN AIR SENSOR
CIRCUIT BREAKER
(FIELD SUPPLY)
UAT240/280/320AY1
BLUE
RED
RED
WHITE
BLACK
Arrangement
ID FAN
BLUE