Daikin FXFQ63PVE [54/90] Fxmq63p 80pve

Daikin FXFQ32PVE [54/90] Fxmq63p 80pve
ED39-865 Dimensions
FXMQ-P (R-410A) 53
2
FXMQ63P / 80PVE
300 or more
150
200
167
245
(Service space)
4
13 × 65=845
950
27
28
700
6
11 × 65=715
(All around)
785
247
1
3 × 65=195
(Service space)
or less
10
49
513
5 × 150=750
300 or less
8
215
2 × 65=130
277
700 or less
700 or more
80
631
(From the Air outlet)
11
212
290
150
3
144
65
925
(All around)
59
18-8 × 12 oblong hole
450 or more
2
150
300
Adjustable
(467 or less)
7
760
9
6 × 150=900
(Suspention bolt position)
232
1038 (Suspention bolt position)
12
26
150
1000
169
(All around)
5
805
Inspection hatch 450 or more
(All around)
16-8 × 12 oblong hole
Air inlet
Floor surface
Air
outlet
Air outlet
435
(From the Air inlet)
30-φ 4.7 hole
36-φ 4.7 hole
Ceilling
View B-1
Control box
CASE 1)
200
or less
Control box
Fig. A
CeilingInspection hatch
Control box
Inspection hatch 2
700
or more
or less
or more
or more
1000
200
CASE 2), 3)
View B-2
Control box
Inspection hatch 3
700
or more
1300
20
Control box
B
or more
Inspection hatch
Ceiling
300
or more
(Note. 4)
2500 or more
(A case without
the ceiling)
Air inlet
(Note. 2)
(SAME AS THE INDOOR
UNIT SIZE OR MORE)
Air
inlet
Air
outlet
(SAME AS THE INDOOR
UNIT SIZE +300 OR MORE)
Unit
base
Inspection hatch 1
(450mm × 450mm)
Inspection hatch 1
(450mm × 450mm)
Notes)1. Location of MANUFACTURE'S LABEL:
Contro box surface
2. Mount the air filter at the suction side.
Select its colorimethod (gravity method)
50% or more.
3. Do not locate things should not be wet
under the indoor unit.
Dews may drop when humidity reaches
over 80%, or a drain gets stuck, or air
filters are not clean.
4. Space for Service Works
1) One inspection hatch (450 × 450) on the control box side
and a space of 300mm or more under the unit. (Fig. A)
2) One inspection hatch (450 × 450) on the control box side
and 2 (two) inspection hatches under the unit. (Arrow
View B-1)
3) 3 (three) inspection hatches under the unit and the
control box. (Arrow View B-2)
According to any one of below 1)~3), secure a space
for service works, such as, checking and maintenance
of control box and drain pumps, etc.
11
Power supply connection
7
Hook
Socket (For maintenance)
Interunit wiring connection
6
Drain pipe connection
3
12
4
φ 15.9 flale connection
ITEM
Control box (Inside)
5
10
PART NAME
M4
VP25 (O. D. φ 32, I. D. φ 25)
VP25 (O. D. φ 32, I. D. φ 25)
For M10
REMARK
Liquid pipe connection
1
O. D. φ 32 (Outlet)
Gas pipe connection
2
Drain hose (Accessory)
Air discharge flange
8
φ 9.5 flale connection
Air suction flange
9
Ground terminal (Terminal in Control box)
View
3D060161C