Daikin FXCQ80AVEB [19/30] 2 electrical characteristics

Daikin FXCQ125AVEB [19/30] 2 electrical characteristics
English 18
Water piping .........Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wiring ......Electric potential may rise abnormally if struck by a
lightning bolt.
For electric wiring work, refer to also the “WIRING DIAGRAM” attached to the control box lid.
Carry out wiring between the outdoor units, indoor units and the remote controllers according to the wiring
diagram.
Carry out installation and wiring of the remote controller according to the “installation manual” attached to
the remote controller.
Do not touch the Printed Circuit Board assembly. It may cause malfunction.
8-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A) ; MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)
8-3 SPECIFICATION FOR FIELD SUPPLY FUSES AND WIRING
The lengths of remote controller wiring and transmission wirings are as follows:
(1) Remote controller wiring (indoor unit - remote controller).......Max. 500m
(2) Transmission wirings........... Total wiring length 2000m
Outdoor unit - Indoor unit ...... Max. 1000m
Outdoor unit - BS unit............ Max. 1000m
BS unit - Indoor unit .............. Max. 1000m
Indoor unit - Indoor unit ......... Max. 1000m
NOTE
1. Shows only in case of protected piping. Use H07RN-F in case of no protection.
2. Vinyl cord with sheath or cable (Insulated thickness : 1mm or more)
Indoor units Power supply Fan motor
Model Hz Volts Voltage range MCA MFA kW FLA
FXCQ20AVEB
50 220-240
Max. 264
Min. 198
0.3 16 0.046 0.2
FXCQ25AVEB 0.3 16 0.046 0.2
FXCQ32AVEB 0.3 16 0.046 0.2
FXCQ40AVEB 0.3 16 0.046 0.2
FXCQ50AVEB 0.4 16 0.046 0.3
FXCQ63AVEB 0.5 16 0.106 0.4
FXCQ80AVEB 0.6 16
0.046
+
0.046
0.5
FXCQ125AVEB 1.1 16
0.106
+
0.106
0.9
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Field fuses
Wiring Size Wiring Size
FXCQ20AVEB
16A
H05VV-U3G
NOTE 1)
Wiring size and
length must
comply with
local codes.
Vinyl cord with
sheath or cable
(2 core)
NOTE 2)
0.75-1.25mm
2
FXCQ25AVEB
FXCQ32AVEB
FXCQ40AVEB
FXCQ50AVEB
FXCQ63AVEB
FXCQ80AVEB
FXCQ125AVEB
01_EN_3P249378-7M.fm Page 18 Wednesday, September 12, 2012 1:05 PM