Daikin FXCQ80AVEB [5/30] 2 optional accessories

Daikin FXCQ125AVEB [5/30] 2 optional accessories
English 4
2-2 OPTIONAL ACCESSORIES
This indoor unit separately requires a decoration panel and a remote controller.
Confirm if a decoration panel shown in the Table 1 is prepared and meets your model.
(Refer to the installation manual attached to the decoration panel for how to install.)
Ta ble 1
There are 2 kinds of remote controller; wired type and wireless type.
Install the remote controller to the place where the customer has given consent.
Refer to the catalog for the applicable model.
(Refer to the installation manual attached to the remote controller for how to install.)
CARRY OUT THE WORK GIVING CAUTION TO THE FOLLOWING ITEMS AND AFTER THE
WORK IS COMPLETED CHECK THESE AGAIN.
1. Items to be checked after the installation work is completed
Make sure to recheck the items of “SAFETY PRECAUTIONS”.
Indoor unit Decoration panel
FXCQ20AVEB
BYBCQ40HW1
FXCQ25AVEB
FXCQ32AVEB
FXCQ40AVEB
FXCQ50AVEB
BYBCQ63HW1
FXCQ63AVEB
FXCQ80AVEB
BYBCQ125HW1
FXCQ125AVEB
Items to be checked In case of defective
Check
column
Are the indoor and outdoor units rigidly fixed? Drop · vibration · noise
Are the installation works of the outdoor and
indoor units completed?
Does not operate · burnout
Have you carried out a leakage test with the
test pressure specified in the outdoor unit
installation manual?
Does not cool / Does not heat
Is the insulation of refrigerant piping and drain
piping completely carried out?
Water leakage
Does the drain flow out smoothly? Water leakage
Is the power supply voltage identical to that
stated in the manufacturer’s label on the air
conditioner?
Does not operate · burnout
Are you sure that there is no wrong wiring or
piping or no loose wiring?
Does not operate · burnout
Is earthing completed? Danger in case of leakage
Are the sizes of electric wiring according to the
specification?
Does not operate · burnout
Is any of air outlets or inlets of the indoor and
outdoor units blocked with obstacles?
(It may lead to capacity drop due to fan speed
drop or malfunction of equipment.)
Does not cool / Does not heat
Have you recorded the refrigerant piping length
and the refrigerant charge added?
Refrigerant charge amount is not clear
01_EN_3P249378-7M.fm Page 4 Wednesday, September 12, 2012 1:05 PM