Daikin FXCQ80AVEB Инструкция по монтажу онлайн [21/30] 542817

Daikin FXCQ125AVEB Инструкция по монтажу онлайн [21/30] 542819
English 20
After connecting the wiring, make sure to stick the sealing material (12) to the wiring penetrating hole.
(Refer to Fig. 19)
(It is to prevent water from entering into the indoor unit.)
CAUTION
Never connect the power supply wiring to the terminal block for remote controller/transmission wiring (X1M).
If may damage the total system.
Do not connect the remote controller/transmission wiring to the wrong terminal bock.
Earth terminal
To avoid the clamp getting into contact with the
control box lid, place the clamp horizontally
As for the clamp added for preventing gap, clamp it
to the terminal block next to the clamp for fixing
Clamp (4) (accessory)
After the wirings are clamped,
cut off the extra part
10~15mm
20~25mm
Earth wiringTerminal block (X2M)
Sheathed part
60~80mm
(Sheath peeling off allowance)
<<Power supply wiring, Earth wiring>>
Clamp (4) (accessory)
After the wirings are clamped, cut off the extra part
Place the clamp horizontally so that
it may not contact with control box lid
When carrying out crossover, use adjacent wiring clamp
Terminal block (X1M)
Transmission
wirings
Remote controller
Strand the
wirings after
sheath is
peeled off
30~35mm
(Sheath peeling off allowance)
Do not connect power supply
wiring (high voltage)
Prohibited
Sheathed part of remote controller
wiring, transmission wiring
<<Remote controller wiring, Transmission wiring>>
approx. 7mm
N
L
01_EN_3P249378-7M.fm Page 20 Wednesday, September 12, 2012 1:05 PM