Outline of Control (Indoor Unit) SiBE311209
123 Function
If a humidifier is connected and the "Drain pump / Humidifier interlock" parameter is set to
"Enabled" while in filed setting mode, the following control will be conducted.
1. Float switch activation (1), etc.
6: While in operation with thermostat ON, the drain pump repeats 20-min. OFF and 3-min. ON
operation.
7: If the float switch is activated, the drain pump will conduct residual operation for a period of
5 minutes.
8: If the thermostat turns OFF, the drain pump will conduct residual operation for a period of
20 minutes.
2. Float switch activation (2), etc.
9: If the thermostat turns OFF, the drain pump will conduct residual operation for a period of
20 minutes regardless of its operating status.
10:If the float switch is not reset within a period of 5 minutes after it is activated, the remote
controller will display the error code "
A3
" and the system will make a stop due to error.
Thermostat (running)
Humidifier
Float switch
Drain pump
ON
OFF
ON
OFF
OFF
ON
ON
OFF
20 min.
3 min.
20 min.
3 min.
5 min.
5 sec.
20 min.
6
7 8
Thermostat (running)
Humidifier
Float switch
Drain pump
ON
OFF
ON
OFF
OFF
ON
ON
OFF
Stop due to the "
A3
" error of
remote controller
20 min.
5 min.
20 min.
5 sec.
9 10