Daikin FXSQ125P7VEB [169/370] Setting of operation control mode from remote controller field setting

Daikin FXSQ140PVE4 [169/370] Setting of operation control mode from remote controller field setting
SiBE311209 Field Setting
Test Operation 160
Group No. Setting
Example
Caution When turning the power supply ON, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
3.1.8 Setting of Operation Control Mode from Remote Controller
(Field Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor
is connected)
3.1.9 Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with
temperature and operation mode setting by remote controller can be set and displayed by
operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and off by remote
controller only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not
want to start operation by central remote controller when time of system start is
programmed.
Indoor/Outdoor
Outdoor/Outdoor
F1 F2 F1 F2
Indoor/Outdoor
Outdoor/Outdoor
F1 F2 F1 F2
Central Remote
Controller
F1 F2
F1 F2 P1 P2
RC
1-00
F1 F2 P1 P2
RC
1-01
RC
SubMain
F1 F2 P1 P2
RC
1-02
F1 F2 P1 P2
Group Control by Remote
Controller (automatic unit address)
F1 F2 P1 P2
No. of Remote Controller
1-03
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
RC
1-04