Daikin FXSQ125P7VEB [312/370] Troubleshooting

Daikin FXSQ20P7VEB [312/370] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE311209
303 Service Diagnosis
Troubleshooting
Note
1: Check the correct wiring “indoor-outdoor” and “outdoor-outdoor” by Installation manual.
2: What is Auto Address?
This is the address automatically assigned to indoor units and outdoor units after initial power supply upon
installation, or after executing rewiring (Keep pressing the RESET button for more than 4 seconds).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Is electricity being
introduce for the first
time after installation
or after an indoor or
outdoor unit PCB has
been replaced?
Normal
YES
NO
NO
YES
YES
NO
YES
NO
YES
NO
Is indoor - outdoor
and outdoor - outdoor
unit transmission
wiring normal?
Press and hold the RESET
button on the outdoor unit
PCB for 5 seconds.
Does an error
occur?
Disconnect the
outdoor-outdoor unit
transmission wiring to
create the one-
system status, and
then check whether or
not the system is
normal.
Does a “
UH
” error
occur for all indoor
units in the system?
Does an error occur
even after 12 minutes
elapses from the time
when electricity is
introduced to indoor
and outdoor units?
After fixing the incorrect wiring,
press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
The unit will not run for up to
12 minutes.
Normal
Mount the DIII-NET expander
adaptor.
Replace the indoor unit PCB.
Replace the outdoor unit PCB
(A1P or A3P).
YES