Daikin BEVQ100MVE [3/10] Specifications

Daikin BEVQ100MVE [3/10] Specifications
Indoor Units • JUNCTION BOX • BEVQ-MVE
1
1
VRVII Systems • Indoor Units
1
IndoorVRVII BEVQ-MVJuncti
1 Specifications
1-1 TECHNICAL SPECIFICATIONS BEVQ71MVE BEVQ100MVE BEVQ125MVE
Power input
(Nominal)
Cooling kW 0.189 0.298 0.298
Heating kW 0.169 0.278 0.278
Casing Material Galvanised steel plate
Dimensions Unit Height mm 100 100 100
Width mm 350 350 350
Depth mm 225 225 225
Sound absorbing thermal insulation material Flame and heat resistant foamed polyetherene
Weight Machine Weight kg 3.0 3.0 3.5
Indoor Units Liquid (OD) Type Flare connection
Diameter mm 9.5 9.5 9.5
Gas Type Flare connection
Diameter mm 15.9 15.9 15.9
Outdoor Unit Liquid (OD) Type Flare connection
Diameter mm 9.5 9.5 9.5
Suction gas
(OD)
Type Flare connection
Diameter mm 15.9 15.9 15.9
Standard
Accessories
Item Installation manual
Quantity 1 1 1
Item Gas piping connections
Quantity 1 1 1
Item Insulation for fitting
Quantity 3 3 3
Item Sealing material
Quantity 3 3 3
Item Clamps
Quantity 9 9 9
1-2 ELECTRICAL SPECIFICATIONS BEVQ71MVE BEVQ100MVE BEVQ125MVE
Power Supply Name VE
Phase
Frequency Hz 50/60
Voltage V 220-240
Voltage range Minimum V -10%
Maximum V +10%
Total circuit Minimum circuit amps
(MCA)
A0.8 1.3 1.3
Maximum fuse amps (MFA) A 15 15 15
NOTES
1 Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2 Maximum allowable voltage range variation between phases is 2%.
•MCA/MFA
MCA=1.25 X FLA
3 MFA is smaller than or equal to 4 x FLA
4 Next lower standard fuse rating minimum 15A
5 Select wire size based on MCA
6 Instead of a fuse, use a circuit breaker