Daikin RXQ46MAY1 [148/344] A setting mode 1

Daikin RXQ26MAY1 [148/344] A setting mode 1
Si39-501 Field Setting
Test Operation 137
a. Setting mode 1
This mode is used to check the following items.
1. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
The system is normally set to "Setting
mode 1".
Should the system be set to any
mode other than that, press the
MODE (BS1) button to set the
system to "Setting mode 1".
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Pressing the RETURN (BS3) button
will bring the system to the initial
state of "Setting mode 1".
Procedure for checking check items
(V2763)
Page
H1P
Preparation
alarm
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
7787777
Current operating conditions
7Normal 8Abnormal
9In preparation or in check
operation
Setting of COO/HEAT selection
877By individual outdoor
unit
787In a batch of outdoor unit
group with master unit
778In a batch of outdoor unit
group with slave unit
Low noise operating conditions
7In normal operation
8In low noise operation
Demand operating conditions
7In normal operation
8In demand operation

Содержание

Скачать