Daikin RX46MYL [116/255] Led display for master slave judgment malfunctions at the time of test operation

Daikin RX20MY1E [116/255] Led display for master slave judgment malfunctions at the time of test operation
VRV in General SiE30-408
112 Cases for Examination
1.5 LED Display for Master/slave Judgment Malfunctions at
the Time of Test Operation.
Applicable
Models
RX(Y)(Q) ~ M (Outdoor unit multi system of VRV II series)
Condition LED display for master/slave judgment remained to be turned off the test operation of the multi
system of two VRV II units though the unit being connected to the indoor-to-outdoor unit
connection wire should be judged as a master unit normally.
At that time, the same LED for the slave unit of outdoor multi connection was blinking.
Cause Instead of connection of "outdoor multi terminals (Q1 and Q2)", "outdoor-to-outdoor (F1 and
F2)" connection was being applied at the time of multiple operation.
Measure Recovers by correcting the wire connections between outdoor units to "outdoor multi (Q1 and
Q2)".
Point of
Diagnosis
Select the method of connection of outdoor units from the following two methods, A and B.
A. Batch connection between outdoor units of different systems Connect the "Out - Out
terminals (F1 and F2)".
B. Multiple connection of the same system Connect the "outdoor multiple terminals (Q1 and
Q2)".
In - Out
Out - Out
Out - Out
In - Out
[Incorrect] [Correct]
Outdoor
multi
Outdoor
multi