Daikin RX46MYL [183/255] Are discharge superheated degree and suction superheated degree kept at proper levels respectively

Daikin RX26MY1 [183/255] Are discharge superheated degree and suction superheated degree kept at proper levels respectively
SiE30-408 Points of Analysis
Service Checker Type3 Application Edition 179
Pay attention to “Condensing temp./Evaporating temp.” rather than to “High pressure/Low pressure”.
High and low pressures detected by each pressure sensor are displayed in values, converted
into pressure equivalent saturation temperatures, and used as target values for the capacity
control. Therefore, it is immediately obvious whether or not the target temperatures are
achieved.
Check each drooping/protection control for operating conditions and think about why this control is
performed.
Each stepping down/protection control is used to ensure reliability, not to protect malfunctions.
For example, do not consider that “The unit does not cool (or heat) due to control activated”.
Verify why the control is activated, in accordance with other data.
Are “discharge superheated degree and suction superheated degree” kept at proper levels, respectively?
Most of malfunctions on compressors result from “wet operation”. Referring to the diagnosis
procedure on the preceding page, check to be sure the discharge and suction superheated
degrees are kept at proper levels.
Use data on indoor units as reference values.
Data on temperatures and Evs' opening degrees of indoor units are updated every five minutes.
By contrast, data on outdoor units are updated earlier than that. As a result, even though data
on outdoor units can be collected, the data is not synchronized with that while in malfunction in
most cases. Give consideration to this point in order to verify the data on indoor units.