Daikin RX46MYL [65/255] Monitor mode

Daikin RX16MTLE [65/255] Monitor mode
SiE30-408 Field Setting on Outdoor Unit
Field Settings from Remote Controller 61
2.1.3 Monitor Mode
The numbers in the "No." column show the number of times to press the
.
Display contents of setting item No.0 “Various settings”
Explanation of Used Examples
* 1: Use when checking the checker system.
* 2: Check the numbers to connected indoor units for transmission
malfunction, etc.
* 3: Check the malfunction code.
* 4: Check the Retry contents.
* 5: Check when the operation pattern of outdoor unit is unusual.
No.
Setting items
LED display
Data
display
H1P H2P H3P H4P H5P H6P H7P
0 Various settings
9777777
Refer to
below
1
Address in batch cooling /
heating
9777778
Lower six
digits
2 Low noise · Demand address
9777787
4 AirNet address (*1)
9777877
5
The number of connected
indoor units (*2)
9777878
7
The number of connected zone
units (Outdoor, except BS)
9777888
8 The number of outdoor units
9778777
11
The number of zone units
(Outdoor, except BS)
9778788
Lower six
digits
12 The number of terminals
9778877
Lower
four
digits
(upper)
13 The number of terminals
9778878
Lower
four
digits
(lower)
14
Content of malfunction
(latest)
(*3)
8778887
Refer to
page
104,
Malfunc-
tion code
list in the
chapter
of
trouble-
shooting.
15
Content of malfunction
(one cycle before)
8778888
16
Content of malfunction
(two cycles before)
8787777
20 Content of retry (latest)
(*4)
8787877
21
Content of retry (one
cycle before)
8787878
22
Content of retry (two
cycles before)
8787887
Pressing the MODE button (BS1)
while in "Setting mode 1" will enter
"Monitor mode".
<Selection of Setting Item>
Press the SET button (BS2) and set
the LED display to setting items.
<Check the set contents>
Pressing the RETURN button (BS3)
will display respective databy LED.
Pressing the RETURN button (BS3)
will put the system into the initial state
of "Monitor mode".
* Pressing the MODE button (BS1) will
return the system to "Setting mode 1".
SET button
(
BS2
)
Setting of EMG
operation/ backup
operation (*5)
ON
9778777
OFF
9777777
Setting of defrost
selection
Short
time
9777877
Middle
time
9777977
Long
time
9777777
Te setting
H
9777787
M
9777797
L
9777777
Tc setting
H
9777778
M
9777779
L
9777777

Содержание

Скачать