4.5 Unscheduled maintenance
If replacing the
electronic board
, the user MUST set the
parameters as indicated in the table.
Type
No.
Description
Setting for
Brava
Slim HE
25 30 35 40
PAR 01
Index showing boiler power in kW
1 = 25; 2 = 30; 3 = 35; 4 = 40
1 2 3 4
PAR 02
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
heating only
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
6 = boiler with heat pump
0
PAR 03
Gas Type Configuration
0 = G20; 1 = G31
0 or 1
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the entire phase of "Self-calibrating procedure" described
in the specific section.
If the
gas cock
and/or the
ignition/detection electrode
, and/or the
burner
, and/or the
fan
are replaced, the user must still carry out
the entire phase of "Self-calibrating procedure" described in
the specific section.
4.6 Possible faults and solutions
LIST OF MALFUNCTION/FAULT ALARMS
Type No. Fault Solution
ALL 02
Low water pressure
in system
- Restore pressure
- Check for any leaks in the
system
ALL 03
High water pressure
in system
- Empty the system via the
drain valve on the hydraulic
assembly and bring the
pressure to approximately
1.2 bar
ALL 04
Domestic hot water
sensor fault
- Check connections
- Replace the sensor
ALL 05 Delivery sensor fault
- Check connections
- Replace the sensor
ALL 06 No flame detection
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
ALL 07
Sensor or safety
thermostat
intervenes
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump impeller
is not blocked
ALL 08
Fault in the flame
detection circuit
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
ALL 09
No water circulating
in the system
- Check the rotation of the
system pump impeller
- Check the electrical
connections
- Replace the pump
ALL 10 Auxiliary sensor fault
- Check PAR 02 "hydraulic
configuration"
- Check the electrical
connection
Type No. Fault Solution
ALL 11
Gas valve modulator
disconnected
- Check the electrical
connection
ALL 12
Incorrect configuration
of the open /sealed
chamber
- Set the parameter PAR 04
(Combustion configuration)
to 0
ALL 13
Smoke probe
intervention
- Replace the smoke probe
- Contact the Technical
Assistance Centre
ALL 14 Smoke probe fault
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe, if the problem is
not resolved, contact the
Assistance Centre
ALL 15
Fan check cable
disconnected
- Check the connection cable
between the fan and the
board
ALL 18 Condensate level fault
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is not
clogged
ALL 28
Maximum number of
consecutive resets
reached
- Contact the Technical
Assistance Centre
ALL 30
Return sensor (SR)
fault
- Replace the return probe
- Contact the Technical
Assistance Centre
ALL 37
Fault due to low
network voltage.
- Check with tester
- Contact network provider
(ENEL)
ALL 40
Incorrect network
frequency detected
- Contact network provider
(ENEL)
ALL 41
Flame loss more than
6 consecutive times
- Check the detection
electrode
- Check the gas supply (open
valve)
- Check mains gas pressure
ALL 42 Button fault
- Check that buttons are
working
ALL 43
Open Therm
communication fault
- Check the electrical
connection of the remote
control
ALL 62
Self-calibrating
procedure is required
- Carry out the self-
calibrating procedure (see
the specific section)
ALL 72
Incorrect positioning of
the delivery sensor
- Check that the delivery
sensor is attached to the
delivery pipe
ALL 77
EV2 SGV current max/
min absolute limits
error
- Contact the Technical
Assistance Centre
ALL 78
EV2 SGV current upper
limit error
- Contact the Technical
Assistance Centre
ALL 79
EV2 SGV current lower
limit error
- Contact the Technical
Assistance Centre
ALL 80
Fault on the valve
control logic line/valve
cable damaged
- Check the valve cable
- Contact the Technical
Assistance Centre
ALL 81
Block due to
combustion during
start-up
- Check for blockage in
chimney
- Bleed the air from the gas
circuit
ALL 82
Block due to numerous
combustion control
failures
- Check electrode
- Check outlets
ALL 83
Irregular combustion
(temporary error)
- Check for blockage in
chimney
ALL 84
Flow rate reduced
for (presumed) low
pressure on mains gas
- Check gas flow rate
ALL 88
Internal error (board
component protection)
- Contact the Technical
Assistance Centre
ALL 89
Unstable combustion
feedback signal error
- Contact the Technical
Assistance Centre