TRACO POWER TIS75-112 [5/13] Technical specifications

TRACO POWER TIS50-112 [5/13] Technical specifications
Tel: +41 1284 2911
Fax: +41 1201 1168
E-Mail: sales@traco.ch
www.tracopower.com
Date: October 25, 2000
Issue: 1.2
Page
Seite
5
Jenatschstrasse 1
CH-8002 Zürich
Technical Specifications
Input Specifications
Output
voltage
Input current
at full load typ.
Inrush current
max. at +25°C (<2ms)
recommended
Circuit breaker
Order-
Code
Model
Input
voltage
range
max.
Output-
power
Factory Set ±1%
Output
current
max.
115 VAC 230 VAC 115 VAC 230 VAC Characteristic C
Efficiency
typ.
at 230VAC
TIS 75-112
TIS 75-124
TIS 75-148
75 Watt
75 Watt
75 Watt
12 VDC
24 VDC
48 VDC
6.0 A
3.0 A
1.5 A
1.7 A 0.9 A 16.5 A 33.0 A 5.0 A
83.0 %
85.0 %
88.0 %
TIS 150-124
TIS 150-148
150 Watt
150 Watt
24 VDC
48 VDC
6.0 A
3.0 A
3.0 A 1.7 A 35.0 A 70.0 A 10.0 A
84.0 %
88.0 %
TIS 300-124
TIS 300-148
TIS 300-172
300 Watt
300 Watt
300 Watt
24 VDC
48 VDC
72 VDC
12.0 A
6.0 A
4.2 A
5.4 A 3.3 A 35.0 A 70.0 A 15.0 A
87.0 %
89.0 %
91.0 %
TIS 600-124
TIS 600-127
TIS 600-148
TIS 600-172
115/230VAC
selectable
by switch
93-132 VAC
187-264 VAC
(47-63 Hz)
600 Watt
600 Watt
600 Watt
600 Watt
24 VDC
28 VDC
48 VDC
72 VDC
24.0 A
22.0 A
12.0 A
8.5 A
10.5 A 6.4 A 70.0 A 80.0 A 20.0 A
88.0 %
89.0 %
90.0 %
91.0 %
TIS 500-124
230VAC
187-264 VAC
500 Watt 24 VDC
20.0 A
xxxxxx 5.5 A xxxxxx 70.0 A 15.0 A 88.0 %
* For Option UDS, RED and SIG see separate operating instructions.
Output Specifications
Regulation
- Input Variation (Line Regulation)
- Load Variation (Load Regulation)
V
in min
- V
in max
10% - 90% of I
out max
75W and 150W Models
10% - 90% of I
out max
300W, 500W and 600W Models
±0.2% max
±1.0% max
±0.3% max
±1.5% with parallel operation
Output Voltage adjustable Range
with Potentiometer
12 V Model
24 V Model
28 V Model
48 V Model
72 V Model
12 - 14 VDC
24 - 28 VDC
28 - 32 VDC
48 - 52 VDC
60 - 72 VDC
Ripple and Noise
(20MHz Bandwidth)
at V
in nom
und I
out max
<50mVpp
Electronic Current Limitation,
Short Circuit Protection (OCP)
Constant Current Limitation Characteristic 110 % typ.
Automatic restart
Parallel Operation
TIS 75-1xx; User selectable standard mode and
parallel mode by jumper on PCB
TIS 500-124
TIS 150-1xx, TIS 300-1xx and TIS 600-1xx
up to 5 Power Supplies possible
2 power supplies possible
Option RED required
Overvoltage Protection (OVP) Triggerpoint at 140% typ. V
out nom.
Hold - up Time 30 ms min.
General Specifications
Operating Temperature Range -25°C - +70°C
Storage Temperature Range -25°C - +85°C
Load Derating above 50°C 2
%
/
°C
Humidity (non condensing) 95% rel H max.
Switching Frequency all Models 80 kHz typ. (PWM)
Safety class (according to IEC 60536) Class 1
Case protection (according to IEC 60529) IP20
Safety Standards according to
!"
IEC / EN 60950
!"
CB Scheme according to worldwide requirements
!"
UL / cUL 1950 recognised File No.: E181381
!"
UL 508 recognised File No.: E181381
!"
CSA22.2-14 File No.: E181381
Overvoltage category according to EN50178 Category III
Conducted EMI on the Input EN 55022 Class B; EN 55011 Class B; FCC-B
Radiated EMI EN 55022 Class A
Electromagnetic suspectibility
EMC Immunity
Electrostatic discharge (ESD)
RF field suspectibility
Electrical fast transients / Bursts
Surge
Immunity to conducted radio frequency disturbances
Mains frequency field
IEC / EN 61000-4-2 4kV / 8kV
IEC / EN 61000-4-3 10V / m
IEC / EN 61000-4-4 2kV
IEC / EN 61000-4-5 2kV / 4kV
IEC / EN 61000-4-6 10V
IEC / EN 61000-4-8 30A / m
Environment Vibration
Shock
IEC 60068-2-6 1gn, 20 sweeps, each axes
IEC 60068-2-27 15gn, 11ms, each axes
Connections and terminal assignment
Terminals Function Connected load Remarks
L1 & N Input Voltage (115/230VAC) Screw-type terminals
Protective Earth Conductor Use a screwdriver with blade width of 3.5mm (0.1378in)
+ & - Output Voltage (12, 24, 28, 48 & 72VDC)
0.5 ... 6.0mm
2
22 ... 10 AWG
use all terminals
Recommended tightening torque 0.5 to 0.7Nm (4.5 to 6.2lb.in.)
English

Содержание

Скачать