Daikin REMQ16PY1 [372/491] Caution be su re to t u rn off power s witch b efore connect or di s connect connector or p a rt s d a m a ge m a y b e occ u rred

Daikin REMQ8PY1 [372/491] Caution be su re to t u rn off power s witch b efore connect or di s connect connector or p a rt s d a m a ge m a y b e occ u rred
6L(1%( 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWURO
7URXEOHVKRRWLQJ 
7URXEOHVKRRWLQJ
NO
YES
Replace the main PC board of
the outdoor unit.
• With single systems, replace
the control PC board 1 (A1P) or
the control PC board 3 (A3P).
• With multi systems, replace the
main PC board (A1P).
NO
YES
The number of indoor units
exceeds the standard. Check the
connection to correct.
Replace the main PC board of
the outdoor unit.
• With single systems, repl
ace the
control PC board 1 (A1P).
• With multi systems, replace the
main PC board (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.
Check 3 Check 4
Diagnosis Flow 1
Check 3 Check 4
Diagnosis Flow 2
The number of
indoor units connected to
the same refrigerant circurt system
should not be more than
64 units.
Check if the
refrigerant type of the
outdoor unit corresponds to that
of the indoor unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.