Daikin REMQ16PY1 [437/491] 100 125 cla ss

Daikin REMQ10PY1 [437/491] 100 125 cla ss
:LULQJ'LDJUDPVIRU5HIHUHQFH 6L(1%(
 $SSHQGL[
);640009
COLORS:
BLK : BLACK
BLU : BLUE
BRN : BROWN
ORG : ORANGE
PNK : PINK
RED : RED
WHT : WHITE
YLW : YELLOW
NOTES
1. Use copper conductors only.
2. When using a central remote control, see manual for connection to the unit.
3. When installing the electric heater, change the wiring for the heater circuit. The main power supply has to be supplied independently.
4. For high E.S.P. operation, change the wiring connection of x4A as shown on the wiring diagram.
5. When connecting the input wires from outside, “forced off” or “on/off” control operation can be selected by the remote control.
See installation manual for more details.
2TW23776-1D
Field wiring
L : Live
N : Neutral
: Connector
: Wire clamp
: Protective earth (screw)
33H Float switch
A1P Printed circuit board
A2P Therminal board
C1R Capacitor (M1F)
F1U Fuse (250V, 5A)
F2U Field fuse
HAP Light emitting diode
(service monitor-green)
M1F Motor (fan)
M1P Motor (drain pump)
Q2E Earth leak detector
R1T Thermistor (air)
R2T, R3T Thermistor (refrigerant)
RyF1-3 Magnetic relay (Fan)
RyP Magnetic relay (Drain pump)
T1R Transformer (220V-27V)
X1M Terminal strip (power)
X2M Terminal
strip (control)
Y1E Electronic expansion valve
Optional parts
F3-5U Fuse (250V, 16A)
J1EH Electric heater
K1R Magnetic relay (J1EH)
Adapter for wiring
RyC,RyF Magnetic relay
RyH Magnetic relay (J1EH)
F1U,F2U Fuse (250V,5A)
X1A,X2A Connecter (wiring adaptor)
X1M Terminal strip
Connector for optional parts
X16A Connector (wiring adapter)
X18A Connector (wiring adapter for
electronical appendices)
NOTE 5
Input from outside
To central remote
control NOTE 2
Wired remote
control
SWITCH BOX
NOTE 3
Seperate power supply
1N~50Hz 230V
NOTE 4
High E.S.P. operation
80,100,125 CLASS
(90,112,140 CLASS)
Terminals for oparation
indicator
1N~50Hz
230V
Indoor
Fan
operation
Compressor
operation
Adapter for wiring

Содержание