Daikin REYQ16PY1B [129/137] Installation

Daikin REYQ16PY1B [129/137] Installation
Outdoor Units • VRV HEAT RECOVERY • REYQ8-48P7Y1B
1
8
VRV Systems • Outdoor Units
128
8 Installation
8 - 1 Service space
3D051451E
REMQ-P
For single unit installation
<Pattern 1>
For installation in rows
<Pattern 1>
300 or more
10 or more
<Front>
500 or more
10 or more
10 or more
20 or more
<Front>
500 or more
20 or more
10 or more
<Pattern 2>
100 or more
50 or more
100 or more
<Front>
500 or more
100 or more
50 or more
<Pattern 2>
100 or more
<Front>
50 or more
50 or more
500 or more
<Pattern 3>
Wall height unrestricted
300 or more
<Front>
200 or more
<Pattern 3>
Wall height unrestricted
300 or more
400 or more
<Front>
400 or more
200 or more
Notes:
1 Heights of walls in case of Patterns 1 and 2:
Front: 1500 mm
suction side: 500 mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the space to be shown in this drawing.
2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figure
on the right.
3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always
bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
300 or more