Daikin RXYQ192MTJU [15/273] Model selection

Daikin RXYQ168MTJU [15/273] Model selection
Model Selection SiUS39-601
4 General Information
3. Model Selection
VRV Heat Pump Series
Connectable Indoor Units Number and Capacity
Connectable Indoor Unit
Indoor Unit Capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (Btu/h).
The total capacity of connected indoor units must be within a range of 70 to 130% of the rated
capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor units.
Select models so the total capacity of connected indoor units conforms to the specification.
Ton 6 ton 8 ton 12 ton 14 ton 16 ton
System name RXYQ72M RXYQ96M RXYQ144M RXYQ168M RXYQ192M
Outdoor unit 1 RXYQ72M RXYQ96M RXYQ72M RXYQ72M RXYQ96M
Outdoor unit 2
——
RXYQ72M RXYQ96M RXYQ96M
Total number of connectable indoor units 12 16 20 20 20
Total Capacity Index of Indoor Units to be Connected
50.5~93.5 67.5~124.5 101~187 118~218 134.5~249.5
Type Model Name Power Supply
Capacity Range 0.6ton 0.8ton 1ton 1.5ton 2ton 2.5ton 3ton 4ton
VJU
Capacity Index 7.5 9.5 12 18 24 30 36 48
Ceiling Mounted Cassette
Type (Multi Flow)
FXFQ 12M 18M 24M 30M 36M
Slim Ceiling Mounted
Duct Type
FXDQ 07M 09M 12M 18M 24M
Ceiling Mounted Built-In
Type
FXSQ 12M 18M 24M 30M 36M 48M
Ceiling Mounted Duct
Type
FXMQ —————30M36M48M
Ceiling Suspended Type
FXHQ 12M 24M 36M
Wall Mounted Type
FXAQ 07M 09M 12M 18M 24M
Floor Standing Type
FXLQ 12M 18M 24M
Concealed Floor
Standing Type
FXNQ 12M 18M 24M
New refrigerant model code 07 type 09 type 12 type 18 type 24 type 30 type 36 type 48 type
Selecting model capacity
7,500
Btu/h
9,500
Btu/h
12,000
Btu/h
18,000
Btu/h
24,000
Btu/h
30,000
Btu/h
36,000
Btu/h
48,000
Btu/h
Equivalent output 0.6 ton 0.8 ton 1 ton 1.5 ton
2
ton
2.5 ton 3 ton 4 ton

Содержание