Daikin RXQ20PY1 [102/355] Outdoor air processing unit field setting remote control

Daikin RXQ18PY1 [102/355] Outdoor air processing unit field setting remote control
Test Operation SiEN34-705
96 General Information
4.4.1.7 Outdoor Air Processing Unit-Field Setting (Remote Control)
Note) Bold face in indicates the default setting.
Mode
No.
Setting
SW
No.
Setting
contents
Setting position No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
10
(20)
0 Stain of filter 2500hr 1250hr —————————————
3
Filtering
time
cumulation
Display
No
display
—————————————
12
(22)
1
External
ON/OFF
input
Forced
stop
ON-OFF
control
—————————————
5
Power
failure
automatic
reset
Not
equipped
Equipped
—————————————
14
(24)
3
Discharge
temperature
(cooling)
13°C 14 15 16 17 18 19 20 21 22 23 24 25 25 25
4
Discharge
temperature
(heating)
18°C 19 20 21 22 23 24 25 26 27 28 29 30 30 30