Daikin RXQ20PY1 [148/355] Size of main gas and liquid pipes and allowable length

Daikin RXQ18PY1 [148/355] Size of main gas and liquid pipes and allowable length
Appendix SiEN34-705
142 General Information
7.7 Size of Main Gas and Liquid Pipes and Allowable Length
7.7.1 Heat Pump 50Hz/60Hz, Cooling Only 50Hz (RX(Y)Q5~54P, 50PH)
Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pipes
(both gas-side and liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main
pipes.
Diameter of above case
Model Gas Liquid
RX(Y)Q5 Type φ19.1
φ12.7
RX(Y)Q8 Type φ22.2
φ25.4*
φ12.7
RX(Y)Q10 Type
φ15.9
RX(Y)Q12 Type
φ15.9
RX(Y)Q14 Type
RX(Y)Q16 Type
φ31.8*
φ15.9
RX(Y)Q18 Type
φ31.8*
φ19.1
RX(Y)Q34 Type
RX(Y)Q36 Type
RX(Y)Q38 Type
RX(Y)Q40 Type
Model Gas Liquid
φ38.1* φ22.2
φ22.2
φ22.2
φ22.2
RX(Y)Q42 Type
RX(Y)Q44 Type
φ22.2
φ22.2
RX(Y)Q46 Type
φ22.2
*If available on the site, use this size.
Otherwise, it can not be increased.
RX(Y)Q48 Type
RX(Y)Q50 Type
RX(Y)Q52 Type
RX(Y)Q54 Type
Model Gas Liquid
φ22.2
φ22.2
φ22.2
φ22.2
RX(Y)Q20 Type
RX(Y)Q22 Type
RX(Y)Q24 Type
RX(Y)Q26 Type
RX(Y)Q28 Type
Model Gas Liquid
φ31.8* φ19.1
φ31.8* φ19.1
φ19.1
φ38.1* φ22.2
φ38.1* φ22.2
RX(Y)Q30 Type
φ38.1* φ22.2
RX(Y)Q32 Type
φ38.1* φ
22.2
Increase
Indoor unit
The first refrigerant branch kit
Main pipes
Outdoor unit
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased