8 English
Required Conditions Example Drawings
1. It is necessay to increase the pipe size between the first branch
kit and the final branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must
not be increased
2. For calculation of Total extension length, the actual length of
above pipes must be doubled.
(except main pipe and the pipes that are not increased)
3. Indoor unit to the nearest branch kit ≤ 130 ft.
4. The difference between
[Outside unit to the farthest indoor unit]
and [Outside unit to the nearest indoor unit] ≤ 130 ft.
8 b+c+d+e+f+g+p≤ 295 ft.
increase the pipe size of b, c, d, e, f, g
a+b×2+c×2+d×2+e×2+f×2+g×2
+h+i+j+k+l+m+n+p≤ 3280 ft.
h, i, j....... p ≤ 130 ft.
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)-(a+h)≤ 130 ft.
Increase the pipe size as follows
φ3/8 → φ1/2
φ1/2 → φ5/8
φ5/8 → φ3/4
φ3/4 → φ7/8
φ7/8 → φ1*
φ1-1/8 → φ1-1/4*
φ1-3/8 → φ1-1/2*
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
H1
p
Outside unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
*If available on the site, use this size. Otherwise it can not be increased.
How to calculate the
additional refrigerant
to be charged
[HEAT RECOVER SYSTEM]
Additional refrigerant to
be charged : R(lb)
R should be rounded
off in units of 0.1 lb.
R =
(Total length (ft)
of liquid piping
size at φ7/8)
(Total length (ft)
of liquid piping
size at φ5/8)
(Total length (ft)
of liquid piping
size at φ3/8)
(Total length (ft)
of liquid piping
size at φ3/4)
(Total length (ft)
of liquid piping
size at φ1/2)
(Total length (ft)
of liquid piping
size at φ1/4)
0.249
0.121
0.040
0.175
0.081
0.015
1.02
HEAT RECOVER SYSTEM
MODEL NAME
THE AMOUNT OF
REFRIGERANT
REYQ72 ~ 120PAYD
REYQ72 ~ 120PATJ
REYQ144 ~ 192PAYD
REYQ144 ~ 192PATJ
7.9 lb
2.2 lb
REFRIGERANT AMOUNT FOR EXCEEDING
CONNECTION CAPACITY OF INDOOR UNIT
INDOOR CONNECTION
CAPACITY
MORE THAN 100%
120% OR LESS
MORE THAN 120%
130% OR LESS
MODEL NAME
REYQ72 ~ 192PAYD
REYQ72 ~ 192PATJ
1.1 lb
1.1 lb
Example for refrigerant branch using REFNET joint and REFNET heder for systems and each pipe length as shown below.
Outside system : REYQ192PAYD
Total capacity of indoor unit : 116%
a : φ3/4 × 15ft.
b : φ3/4 × 10ft.
c : φ3/8 × 5ft.
d : φ3/8 × 5ft.
e : φ3/8 × 5ft.
f : φ3/8 × 5ft.
g : φ3/8 × 5ft.
h : φ3/8 × 5ft.
i : φ3/8 × 5ft.
j : φ3/8 × 5ft.
k : φ3/8 × 10ft.
l : φ3/8 × 10ft.
m : φ3/8 × 10ft.
n : φ3/8 × 5ft.
o : φ1/4 × 5ft.
p : φ1/4 × 5ft.
r : φ1/2 × 1ft.
s : φ3/8 × 1ft.
t : φ3/8 × 1ft.
u : φ5/8 × 1ft.
Note 1.
When the equivalent pipe length between outside and indoor units is 295 ft or more,
the size of main pipes on the liquid side (refer to figure 15)
must be increased according to the right table.
(Never inxrease suction gas pipe and HP/LP gas pipe.)
(Refer to figure 15)
1.Outdoor unit
2.Main pipes
3.Increase only liquid pipe size
4.First refrigerant branch kit
5.BS unit
6.Indoor unit
Note 2.
Allowable length after the first refrigerant branch kit to indoor units is 130 ft or less, however it can be extended up to 295 ft
if all the following conditions are satisfied. (In case of "Branch with REFNET joint")
System
REYQ72 · 96PA type
REYQ120 · 144PA type
REYQ168 ~ 192PA type
Liquid pipe
φ3/8 → φ1/2
φ1/2 → φ5/8
φ5/8 → φ3/4
R = ( 25 × 0.175 + 1 × 0.121 + 1 × 0.081 + 75 × 0.040 + 10 × 0.015 ) × 1.02 + 2.2 + 1.1
a, b u r c~n, s, t o, p
REYQ192PAYD
116%
= 11.182 11.1lb
Round off in units of 0.1 lb.
Содержание
- Installation manual 1
- System air conditioner 1
- Figure 1 figure 3 figure 2 2
- Figure 11 2
- Figure 12 2
- Figure 4 figure 6 figure 5 2
- Figure 7 figure 8 figure 9 figure 10 2
- Figure 13 figure 14 3
- Figure 15 3
- Figure 16 figure 17 2 3
- Figure 17 1 3
- Figure 18 3
- Figure 19 3
- Figure 20 figure 22 3
- Figure 21 3
- Figure 23 4
- Figure 24 4
- Figure 25 4
- Figure 26 4
- Figure 27 figure 29 4
- Figure 28 4
- Figure 30 4
- Figure 31 4
- 1 safety considerations 5
- Contents 5
- English 1 5
- First of all 5
- 2 special notice of product 6
- English 6
- 1 combination 7
- 2 standard supplied accessories 7
- 3 disposal requirements 7
- 3 option accessory 7
- 4 technical and electrical specifications 7
- 5 main components 7
- English 3 7
- Introduction 7
- Selection of location 7
- 1 selection of piping material and refrigerant branching kit 8
- 1 selection of piping material and refrigerantbranching kit 8
- English 8
- Inspecting and handling the unit 8
- Placing the unit 8
- Refrigerant piping 8
- 2 protection against contamination when installing pipes 9
- 2 protection against contaminationwhen installing pipes 9
- 3 pipe connection 9
- 4 connecting the refrigerant piping 9
- English 5 9
- 1 indicate the outside unit multi connection piping kit 2 in case of multi outdoor system re read outside unit to the first outside unit multi connection piping kit as seen from the indoor unit 10
- 5 example of connection 10
- Actual and equivalent pipe length 10
- Actual pipe length 10
- Actual pipe length equivalent length 10
- Actual pipe length from first refrigerant branch kit either refnet joint or refnet header to indoor unit 130 ft note 2 example 8 b c d e s 130 ft 10
- Allowable length after the branch 10
- Between outside unit 2 and indoor unit 10
- Bold 3 pipes 10
- Branch with refnet joint branch with refnet joint and header branch with refnet header 10
- Bs unit 10
- Difference in height between outside unit and indoor unit h1 164 ft max 130 ft if the outside unit is below difference in height between adjacent indoor units h2 49 ft difference in height between adjacent outside units h3 16 ft 10
- English 10
- Example 6 b 130 ft 8 m n p 130 ft example 8 o 10
- Example 8 a o 10
- Example of connection connection of 8 indoor units 10
- First outside unit multi connection piping kit 10
- Ft equivalent pipe length between outside unit 2 and indoor unit 620 ft note 1 10
- Indoor unit cool heat selection possible 10
- Indoor unit cooling only 10
- Indoor unit side 2 pipes 10
- Multi outside system 10
- Outside unit 10
- Outside unit outside unit 10
- Outside unit side 3 pipes 10
- Pipe length between outside unit 2 and indoor unit 540 ft example 8 a b c d e 540 ft 10
- Piping from bs unit to indoor unit or piping from refrigerant branch kit to indoor unit used as cooling only 10
- Piping from outside unit to bs unit 10
- Single outside system 10
- Suction gas pipe hp lp gas pipe liquid pipe 10
- Suction gas pipe liquid pipe 10
- Thin 2 pipes 10
- Total piping length from outside unit 2 to all indoor unit 3280 ft actual pipe length from first outside unit multi connection piping kit to outside unit 33 ft equivalent pipe length from first outside unit multi connection piping kit to outside unit 43 ft 10
- English 7 11
- Outside unit multi connection piping kit and refrigerant branch kit selection 11
- Pipe size selection 11
- 0 75 1 0 21 1 0 81 75 0 40 10 0 15 1 2 2 1 12
- 11 82 11 lb 12
- A b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 3280 ft 12
- A b u r c n s t o p 12
- English 12
- How to calculate the additional refrigerant to be charged 12
- If available on the site use this size otherwise it can not be increased 12
- Increase the pipe size as follows 12
- Indoor units 1 8 12
- Outside unit refnet joint a g 12
- Required conditions example drawings 12
- Round off in units of 0 lb 12
- The farthest indoor unit 8 the nearest indoor unit 1 12
- Φ 3 8 φ 1 2 φ 1 2 φ 5 8 φ 5 8 φ 3 4 φ 3 4 φ 7 8 φ 7 8 φ 1 φ 1 1 8 φ 1 1 4 φ 1 3 8 φ 1 1 2 12
- 1 power circuit safety device and cable requirements 13
- 1 power circuit safety device and cablerequirements 13
- 2 wiring connection example for whole system 13
- 3 leading wire procedure 13
- English 9 13
- Field wiring 13
- 4 transmission wiring connection procedure 14
- 5 power wiring connection procedure 14
- Crimp style terminal 14
- Cup washer 14
- Cut out section 14
- English 14
- Power wire crimp style terminal 14
- 6 procedure for wiring inside units 15
- Air tight test and vacuum drying 15
- English 11 15
- R410a label 15
- Resin hook 15
- Terminal block crip style terminal wire narrow wire thick 15
- 1 before working 16
- Additional refrigerant charge and check operation 16
- Additional refrigerant chargeand check operation 16
- Checking of device and installa tion conditions 16
- Checking of device and installationconditions 16
- English 16
- Pipe insulation 16
- 2 procedure of adding refrigerant charging and check operation 17
- 2 procedure of adding refrigerant charging andcheck operation 17
- English 13 17
- H h i h h h h 17
- J h h h h h h 17
- J h h h i h i 17
- J h h i h h h 17
- J h j h j j h 17
- 2 1 procedure of adding refrigerant charging 18
- Cooling mode 18
- English 18
- H h i h h h h 18
- Heating mode 18
- Less than above range 18
- Outdoor temp 32 f db 109 f db indoor temp 50 f db 90 f db 18
- English 15 19
- 1 before test run 20
- 2 2 procedure of check operation 20
- 2 test run 20
- English 20
- Onsite settings 20
- Test run 20
- 3 checks after test run 21
- Caution for refrigerant leaks 21
- English 17 21
- P215731 8m em09a062a 22
Похожие устройства
- Daikin REYQ120PAYD Спецификация
- Daikin REYQ120PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ120PAYD Инструкция по монтажу
- Daikin REYQ144PAYD Спецификация
- Daikin REYQ144PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ144PAYD Инструкция по монтажу
- Daikin REYQ192PAYD Спецификация
- Daikin REYQ192PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ168PAYD Спецификация
- Daikin REYQ168PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ192PAYD Инструкция по монтажу
- Daikin REYQ168PAYD Инструкция по монтажу
- Daikin RXYQ144PAYD Спецификация
- Daikin RXYQ144PAYD Руководство по вводу в эксплуатацию
- Daikin RXYQ144PAYD Инструкция по монтажу
- SilverStone TJ08 Техническая информация
- SilverStone TJ08 Инструкция по эксплуатации
- SilverStone SST-TJ08B Инструкция по эксплуатации
- SilverStone SST-TJ08B Техническая информация
- SilverStone SST-TJ08S Инструкция по эксплуатации