Daikin REYQ96PAYD [13/22] Field wiring
![Daikin REYQ96PATJ [13/22] Field wiring](/views2/1718197/page13/bgd.png)
English 9
7. FIELD WIRING
NOTE
• All field wiring and components must be installed by a licensed elec-
trician and must comply with relevant local and national regulations.
• Be sure to use a dedicated power circuit. Never use a power supply
shared by another appliance.
• Never install a phase advancing capacitor. As this unit is equipped
with an inverter, installing a phase advancing capacitor will not only
deteriorate power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-frequency waves.
• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and national
regulations.
• This machine includes an inverter device. Connect earth and leave
charge to eliminate the impact on other devices by reducing noise
generated from the inverter device and to prevent leaked current
from being charged in the outer hull of the product.
• Do not connect the ground wire to gas pipes, sewage pipes, lightning
rods, or telephone ground wires.
Gas pipes : can explode or catch fire if there is a gas leak.
Sewage pipes : no grounding effect is possible if hard plastic piping
is used.
Telephone ground wires and lightning rods : dangerous when
struck by lightning due to abnormal rise in electrical potential in the
grounding.
• Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit breaker
that be capable of handling high harmonics in order to prevent mal-
functioning of the earth leakage circuit breaker itself.
• Earth leakage circuit breaker which are especially for protecting
ground-faults should be used in conjunction with main switch or fuse
for use with wiring.
• Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.
• Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may
be broken down.)
• Never remove thermistor, sensor or etc. when connecting power wir-
ing and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compressor
may be broken down.)
• This product have reversed phase protection detector that only
works when the power is turned on. If there exists blackout or the
power goes on and off which the product is operating, attach a
reversed phase protection circuit locally. Running the product in
reversed phase may break the compressor and other parts.
• Attach the power wire securely. Introducing power with a missing N-
phase or with a mistaken N-phase will break the unit.
• Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.
• Make sure the electrical unbalance ratio is no greater than 2%. If it is
larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with attached
clamp without applying external pressure on the terminal parts (terminal
for power wiring, terminal for transmission wiring and earth terminal).
• If there exists the possibility of reversed phase, lose phase, momen-
tary blackout or the power goes on and off while the product is oper-
ating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor
and other parts.
7-1 Power circuit, safety device and cable
requirements
• A power circuit (see the following table) must be provided for connec-
tion of the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage circuit breaker.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (0.1 second or less) 200mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with rel-
evant local and national regulations.
• Specifications for local wiring power cord and branch wiring are in
compliance with local cord.
7-2 Wiring Connection Example for Whole System
(Refer to figure 16)
1. Power supply
2. Main switch
3. Earth leakage circuit breaker
4. Fuse
5. Outside unit
6. COOL/HEAT selector
7. Remote controller
8. Indoor unit
9. BS unit
NOTE
•
Make sure the weak electric wiring (i.e. for the remote controller, between
units, etc.) and the power wiring do not pass near each other, keeping
them at least 2 in. apart.
Proximity may cause electrical interference, malfunctions, and breakage.
• Be sure to connect the power wiring to the power wiring terminal
block and secure it as described in “7-5 Power Wiring Connection
Procedure”.
• Transmission wiring should be secured as described in “7-4 Trans-
mission Wiring Connection Procedure”.
• Secure wiring with clamp such as insulation lock ties to avoid contact
with piping.
• Shape the wires to prevent the structure such as the EL. COMPO.
BOX lid deforming. And close the cover firmly.
• All field wiring is to be procured on site.
7-3 Leading wire Procedure
• The power wiring and ground wiring are passed out from the power
wiring hole on the sides, the front (knock hole) or the bottom frame
(knock hole) .
• The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit or from a piping hole.
(Refer to figure 17-1)
1. Electric wiring diagram
Printed on the back of the EL.COMPO.BOX lid.
2. Knockout hole
3. Power line
4. Transmission line
(Refer to figure 17-2)
1. EL.COMPO.BOX lid
2. Service lid
3. [Service precautions] Label location
Phase and
frequency
Voltage
Minimum
circuit amp.
Recom-
mended fuses
Transmission
line selection
REYQ72PAYD
φ 3, 60Hz 460V 16.0A 20A AWG18-16
REYQ96PAYD
φ 3, 60Hz 460V 20.4A 25A AWG18-16
REYQ120PAYD
φ 3, 60Hz 460V 20.5A 25A AWG18-16
REYQ144PAYD
φ 3, 60Hz 460V 33.4A 25A+25A AWG18-16
REYQ168PAYD
φ 3, 60Hz 460V 37.0A 25A+25A AWG18-16
REYQ192PAYD
φ 3, 60Hz 460V 40.6A 25A+25A AWG18-16
Phase and
frequency
Voltage
Minimum
circuit amp.
Recom-
mended fuses
Transmission
line selection
REYQ72PATJ
φ 3, 60Hz
208-
230V
36.1A 40A AWG18-16
REYQ96PATJ
φ 3, 60Hz
208-
230V
43.8A 45A AWG18-16
REYQ120PATJ
φ 3, 60Hz
208-
230V
44.2A 50A AWG18-16
REYQ144PATJ
φ 3, 60Hz
208-
230V
57.6A 40A+40A AWG18-16
REYQ168PATJ
φ 3, 60Hz
208-
230V
64.9A 40A+50A AWG18-16
REYQ192PATJ
φ 3, 60Hz
208-
230V
72.2A 50A+50A AWG18-16
Содержание
- Installation manual 1
- System air conditioner 1
- Figure 1 figure 3 figure 2 2
- Figure 11 2
- Figure 12 2
- Figure 4 figure 6 figure 5 2
- Figure 7 figure 8 figure 9 figure 10 2
- Figure 13 figure 14 3
- Figure 15 3
- Figure 16 figure 17 2 3
- Figure 17 1 3
- Figure 18 3
- Figure 19 3
- Figure 20 figure 22 3
- Figure 21 3
- Figure 23 4
- Figure 24 4
- Figure 25 4
- Figure 26 4
- Figure 27 figure 29 4
- Figure 28 4
- Figure 30 4
- Figure 31 4
- 1 safety considerations 5
- Contents 5
- English 1 5
- First of all 5
- 2 special notice of product 6
- English 6
- 1 combination 7
- 2 standard supplied accessories 7
- 3 disposal requirements 7
- 3 option accessory 7
- 4 technical and electrical specifications 7
- 5 main components 7
- English 3 7
- Introduction 7
- Selection of location 7
- 1 selection of piping material and refrigerant branching kit 8
- 1 selection of piping material and refrigerantbranching kit 8
- English 8
- Inspecting and handling the unit 8
- Placing the unit 8
- Refrigerant piping 8
- 2 protection against contamination when installing pipes 9
- 2 protection against contaminationwhen installing pipes 9
- 3 pipe connection 9
- 4 connecting the refrigerant piping 9
- English 5 9
- 1 indicate the outside unit multi connection piping kit 2 in case of multi outdoor system re read outside unit to the first outside unit multi connection piping kit as seen from the indoor unit 10
- 5 example of connection 10
- Actual and equivalent pipe length 10
- Actual pipe length 10
- Actual pipe length equivalent length 10
- Actual pipe length from first refrigerant branch kit either refnet joint or refnet header to indoor unit 130 ft note 2 example 8 b c d e s 130 ft 10
- Allowable length after the branch 10
- Between outside unit 2 and indoor unit 10
- Bold 3 pipes 10
- Branch with refnet joint branch with refnet joint and header branch with refnet header 10
- Bs unit 10
- Difference in height between outside unit and indoor unit h1 164 ft max 130 ft if the outside unit is below difference in height between adjacent indoor units h2 49 ft difference in height between adjacent outside units h3 16 ft 10
- English 10
- Example 6 b 130 ft 8 m n p 130 ft example 8 o 10
- Example 8 a o 10
- Example of connection connection of 8 indoor units 10
- First outside unit multi connection piping kit 10
- Ft equivalent pipe length between outside unit 2 and indoor unit 620 ft note 1 10
- Indoor unit cool heat selection possible 10
- Indoor unit cooling only 10
- Indoor unit side 2 pipes 10
- Multi outside system 10
- Outside unit 10
- Outside unit outside unit 10
- Outside unit side 3 pipes 10
- Pipe length between outside unit 2 and indoor unit 540 ft example 8 a b c d e 540 ft 10
- Piping from bs unit to indoor unit or piping from refrigerant branch kit to indoor unit used as cooling only 10
- Piping from outside unit to bs unit 10
- Single outside system 10
- Suction gas pipe hp lp gas pipe liquid pipe 10
- Suction gas pipe liquid pipe 10
- Thin 2 pipes 10
- Total piping length from outside unit 2 to all indoor unit 3280 ft actual pipe length from first outside unit multi connection piping kit to outside unit 33 ft equivalent pipe length from first outside unit multi connection piping kit to outside unit 43 ft 10
- English 7 11
- Outside unit multi connection piping kit and refrigerant branch kit selection 11
- Pipe size selection 11
- 0 75 1 0 21 1 0 81 75 0 40 10 0 15 1 2 2 1 12
- 11 82 11 lb 12
- A b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 3280 ft 12
- A b u r c n s t o p 12
- English 12
- How to calculate the additional refrigerant to be charged 12
- If available on the site use this size otherwise it can not be increased 12
- Increase the pipe size as follows 12
- Indoor units 1 8 12
- Outside unit refnet joint a g 12
- Required conditions example drawings 12
- Round off in units of 0 lb 12
- The farthest indoor unit 8 the nearest indoor unit 1 12
- Φ 3 8 φ 1 2 φ 1 2 φ 5 8 φ 5 8 φ 3 4 φ 3 4 φ 7 8 φ 7 8 φ 1 φ 1 1 8 φ 1 1 4 φ 1 3 8 φ 1 1 2 12
- 1 power circuit safety device and cable requirements 13
- 1 power circuit safety device and cablerequirements 13
- 2 wiring connection example for whole system 13
- 3 leading wire procedure 13
- English 9 13
- Field wiring 13
- 4 transmission wiring connection procedure 14
- 5 power wiring connection procedure 14
- Crimp style terminal 14
- Cup washer 14
- Cut out section 14
- English 14
- Power wire crimp style terminal 14
- 6 procedure for wiring inside units 15
- Air tight test and vacuum drying 15
- English 11 15
- R410a label 15
- Resin hook 15
- Terminal block crip style terminal wire narrow wire thick 15
- 1 before working 16
- Additional refrigerant charge and check operation 16
- Additional refrigerant chargeand check operation 16
- Checking of device and installa tion conditions 16
- Checking of device and installationconditions 16
- English 16
- Pipe insulation 16
- 2 procedure of adding refrigerant charging and check operation 17
- 2 procedure of adding refrigerant charging andcheck operation 17
- English 13 17
- H h i h h h h 17
- J h h h h h h 17
- J h h h i h i 17
- J h h i h h h 17
- J h j h j j h 17
- 2 1 procedure of adding refrigerant charging 18
- Cooling mode 18
- English 18
- H h i h h h h 18
- Heating mode 18
- Less than above range 18
- Outdoor temp 32 f db 109 f db indoor temp 50 f db 90 f db 18
- English 15 19
- 1 before test run 20
- 2 2 procedure of check operation 20
- 2 test run 20
- English 20
- Onsite settings 20
- Test run 20
- 3 checks after test run 21
- Caution for refrigerant leaks 21
- English 17 21
- P215731 8m em09a062a 22
Похожие устройства
- Daikin REYQ120PAYD Спецификация
- Daikin REYQ120PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ120PAYD Инструкция по монтажу
- Daikin REYQ144PAYD Спецификация
- Daikin REYQ144PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ144PAYD Инструкция по монтажу
- Daikin REYQ192PAYD Спецификация
- Daikin REYQ192PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ168PAYD Спецификация
- Daikin REYQ168PAYD Руководство по вводу в эксплуатацию
- Daikin REYQ192PAYD Инструкция по монтажу
- Daikin REYQ168PAYD Инструкция по монтажу
- Daikin RXYQ144PAYD Спецификация
- Daikin RXYQ144PAYD Руководство по вводу в эксплуатацию
- Daikin RXYQ144PAYD Инструкция по монтажу
- SilverStone TJ08 Техническая информация
- SilverStone TJ08 Инструкция по эксплуатации
- SilverStone SST-TJ08B Инструкция по эксплуатации
- SilverStone SST-TJ08B Техническая информация
- SilverStone SST-TJ08S Инструкция по эксплуатации