Optimus Drive PDM20-2S1R5 [39/54] Acceleration deceleration time setting of the pump s moto

Optimus Drive PDM20-2S1R5 [39/54] Acceleration deceleration time setting of the pump s moto
PDM20 Series
- 38 -
P0.34
Lower limit of
AI input signal
0.0
P0.35
V/mA 4.00 Used to correct lower limit of AI signal
P0.35
Upper limit of
AI input signal
P0.34
20
V/mA 20.00 Used to correct upper limit of AI signal
If you find there is some deviation between sensor feedback pressure and feedback
pressure displayed on SPD, adjust above parameter to correct the sensor.
Note: the unit of current sensor is 4~20mA; that of voltage sensor is 0~10V.
P0.36 Acceleration time
0.13600
s 5.0
P0.37 Deceleration time
0.13600
s 3.0
Acceleration/deceleration time setting of the pump’s motor.
P0.38 Parameter initialization
02
0
When P0.38 is set as 1, restore factory defaults.
P0.39 Parameter lock function
01
0
After setting parameters, if you don’t want them to be modified by misoperation,
make P0.39= 1. At this time, parameters can only be monitored, but not be modified.
Only when P0.39 is modified to 0, can parameters be modified.
P0.40 Current fault type
029
Record fault type of the SPD. 0 means no fault. 129 refers to E001E029. For
more details, please refer to fault inspection and troubleshooting chapter.
P1.34
Start/stop signal
choices
01
0
0Start/stop by keyboard
1Start/stop by terminals
P0.43
Frequency source
choices
08 8
0Digital setting
17Reserved
8Water supply PID