ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting 205
3.16
E6
” Outdoor Unit: STD Compressor Motor Overcurrent/
Lock
Remote Control
Display
E6
Applicable
Models
ERQ 125 ~ 250 A7W1
Method of
Malfunction
Detection
Detects the overcurrent with current sensor (CT).
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
400 V unit: 15.0 A
Supposed
Causes
Closed stop value
Obstacles at the air outlet
Improper power voltage
Faulty magnetic switch
Faulty compressor
Faulty current sensor (A6P, A7P)
Troubleshooting
Note: 1 Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0A during STD compressor stop.
NO
YES
NO
NO
NO
YES
NO
NO
Check the wiring from power supply ~ current sensor (A6P, A7P) ~
MgS (K2M, K3M) ~ compressor
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the stop
valve open?
(V3051)
YES
YES
YES
YES
Obstacle exists
around the air outlet.
Is the power
supply voltage normal?
Is the
magnetic switch (K2M,
K3M) normal?
Open the stop valve.
Remove the obstacle.
Correct the power voltage.
Replace the magnetic
switch.
Correct wiring.
Replace the corresponding
current sensor (A6P or
A7P).
Replace compressor.
Is above wiring
correct?
Is current
sensor correct? 1