11 ■English
Connecting the Humidifying Hose
1.
Connecting to indoor unit.
Keep the following items in mind in order to prevent the degrading of humidification performance when connecting the humidifying
hose to the indoor unit.
1) Cut the excessive portions of the humidifying hoses.
* Determine the overall length of the humidifying hoses according to the installation manual for the indoor unit.
2) Be sure to avoid traps as much as possible when installing the humidifying hoses.
3) Be careful not to crush the humidifying hoses in the case of bending the hoses at the time of
installation. Furthermore, make sure that the maximum bending radius will not exceed 90°.
4) Check that the overall length of the humidifying hoses is definitely 3m or more.
5) Attach a cover to the end of each humidifying hose so that no moisture or foreign substance
will go into the hose when leaving the hose without being connected to the outdoor and
indoor units.
Humidifying
hose
Cover
■ Connecting KPMH996A10S (10m set)
Outdoor Indoor
<Indoor unit>
• Make sure that the number of bending times will not exceed the
following limits at the time of installation.
3m-8m :3 times
8.1m-10m :4 times
10.1m-15m :5 times
• Use the KPMH996A15S (15m set) only if the overall length of
the humidifying hoses exceeds 10m.
Mark the cuff on the indoor unit side so
that the overall length of the hoses after
adjustment will be clearly known.
CAUTION
Connect the humidifying hose according to
the installation manual for the indoor unit.
Use the provided joint to connect the humidifying hoses.
Insert the joint into the humidifying hoses so that there
will be no clearance between the hoses on the joint,
and secure the position of 10mm from the end of each
hose with a binding band.
B
Binding
band
Connect the hose
according to the
instructions on page 12
of this manual.
<Outdoor unit>
■ Connecting KPMH996A15S (15m set)
Indoor unit
Outdoor unit
1) Be sure to connect the 8m hose to the indoor unit and
the 2m hose to the outdoor unit, respectively, and join
the 2 hoses with the joint.
A
C
D
D
2m
C
8m
A
Joint
C
• Cut the 8m hose to adjust the overall length of the
humidifying hoses.
• Use the KPMH996A15S (15m set) only if the overall length of the
humidifying hoses exceeds 10m.
1) Be sure to connect one of the 2m hoses (provided with a cuff each) to
the indoor unit and the other one to the outdoor unit.
Connect the 7.5m hose and 3.5m hose midway to adjust the overall
length.
H
J
D
G
Reducing joint
J
3.5m
H
7.5m
G
Reducing joint
D
2m
D
2m
Outdoor unit
Indoor unit
H
H
• Connect the 2 2m hoses (provided
with a cuff each) and the 7.5m
hose all together through the
reducing joint if the overall length of
the humidifying hoses is 11.5m or
less.
• Cut the 7.5m hose to adjust the
overall length of the humidifying
hoses.
G
D
01_EN_3P234246-1.fm Page 11 Thursday, November 6, 2008 9:42 PM
Содержание
- Installation manual r410a split series 1
- Models 1
- Mxu40gv1b 2mxu50gv1b 1
- Outdoor unit 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 3
- English 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Caution 4
- English 4
- English 2 4
- Precautions for selecting the location 4
- Caution 5
- Outdoor unit installation drawings 5
- Precautions for humidifying hose installation work 5
- Connections connection port 6
- English 4 6
- How to use reducers 6
- Installation 6
- Precautions on installation 6
- English 7
- If the outdoor unit is positioned higher than the indoor units if the outdoor unit is positioned otherwise if lower than one or more indoor units 7
- Outdoor unit installation guideline 7
- Piping to each indoor unit room a b 15m max 7
- Selecting a location for installation of the indoor units 7
- The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed below the shorter the refrigerant piping the better the performance connect so that the piping is as short as possible shortest allow able length per room is 3m 7
- Total length of piping between all units 30m max 7
- Wall facing one side 7
- Walls facing three sides 7
- Walls facing two sides 7
- Where a wall or other obstacle is in the path of outdoor unit s intake or exhaust airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 7
- Caution 8
- Drain work 8
- Installing outdoor unit 8
- Refrigerant piping 8
- Refrigerant piping work 8
- Purging air and checking gas leakage 9
- Refrigerant piping work 9
- Warning 9
- Caution 10
- Charging with refrigerant 10
- Important information regarding the refrigerant used 10
- Refilling the refrigerant 10
- English 11
- Precautions for laying refrigerant piping 11
- Refrigerant piping work 11
- Warning 11
- Caution 12
- Connecting the humidifying hose 12
- Forced cooling operation 12
- Pump down operation 12
- Caution 13
- Connecting the humidifying hose 13
- Connecting to indoor unit 13
- Connecting to outdoor unit 14
- English 14
- English 12 14
- Caution 15
- English 15
- Ok ng ok ng 15
- Warning 15
- Wiring 15
- English 14 16
- Items to check 16
- Test run and final check 16
- P234246 1 m08b112 17
Похожие устройства
- Daikin 2MXU50GV1B Технические данные
- Daikin 2MXU40GV1B Инструкция по монтажу
- Daikin 2MXU40GV1B Технические данные
- Daikin 2MXU50GV1B Сервис мануал
- Daikin 2MXU40GV1B Сервис мануал
- Daikin FHC50KVE Сервис мануал
- Daikin FHC50KVE Инструкция по эксплуатации
- Daikin FHC35KVE Сервис мануал
- Daikin FHC35KVE Инструкция по эксплуатации
- Daikin FHC60KVE Сервис мануал
- Daikin FHC60KVE Инструкция по эксплуатации
- Daikin FHYC71KVE Сервис мануал
- Daikin FHYC100KVE Сервис мануал
- Daikin FHYC100KVE Инструкция по эксплуатации
- Daikin FHYC125KVE Сервис мануал
- Daikin FHYC140KVE Сервис мануал
- Daikin FHYC125KVE Инструкция по эксплуатации
- Daikin FHYC140KVE Инструкция по эксплуатации
- Daikin FHYC71KVE Инструкция по эксплуатации
- Daikin FH35BVE Руководство по эксплуатации