Daikin FHYB100FVAL [192/244] Removal of outdoor unit fan and fan motor

Daikin FHK35FJV1 [192/244] Removal of outdoor unit fan and fan motor
Si-71A For R(Y)71K
Removal Procedure 181
6.2 Removal of Outdoor Unit Fan and Fan Motor
Procedure
Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
Remove the front piping cover,
etc., according to the procedure for
removing the external casing.
1 Remove the 4 screws and
disconnect the 8 tabs
fastening the air discharge
grille on the top/bottom and
left/right, and remove the air
discharge grille.
2 Remove the fan clamp
fastening the propeller fan;
remove the nut and washer.
Note:
The fan motor’s lead wire cannot be
disconnected as is. You must first
remove the screw on the right side of
the front casing (1).
3 Disconnect the motor
connector from the PC
board’s wiring connector,
and remove the condenser.