Daikin RZQG71L8Y1B [94/215] Defrost start setting

Daikin RZQG71L8Y1B [94/215] Defrost start setting
Field Setting from Remote Controller ESIE15-13C
80 Field Setting
Graph 3 Target evaporating temperature control when "low humidity application + freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Change
thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the
rise of temperature after thermostat OFF, the thermostat control will be changed when using
field settings 16(26)-2-03 & 16(26)-2-04.
Thermostat ON Trs 0.5 °C (No change from standard setting)
Thermostat OFF Trs -2.0 °C for 5 minutes continuously.
Trs 4.5 °C
2.8 Defrost Start Setting
Refer to “Defrost Operation” on page 48.
2.9 Slow start
Refer to “Slow start for EDP applications” on page 54.
Te target
(˚C)
Te target acceptable area
Remote
controller setting temp.
Te target limited 20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp. > setting Te target down
Indoor temp. < setting Te target up
Te target limited 2˚C
(not to freeze)
Freeze protection
(40min. integrated coil temp. -1˚C)
Indoor Temp
(˚C DB)

Содержание

Похожие устройства

Скачать