Facility Setting
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in
a residence or office (the space where there is a human).
n Cutting jumper 4 (J4)
on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor
temperature drops below –20°C and start back up once the temperature rises again.
1) Remove the two screws on the side and remove the top plate of the outdoor unit.
2) Remove one screw from the upper electric box cover.
3) Remove the upper electric box cover by sliding it, being careful not to bend the electric box hook.
4) Remove the lower electric box cover.
5) Cut the jumper (J4) of the PCB inside.
6) Go back through step 4)
→
3)
→
2)
→
1). Make sure all components are well secured when doing this.
CAUTION
1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4) Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.
5) When removing the upper electric box cover, be careful not to bend the hook.
6) When returning the lower electric box cover, return the notch to the stop valve side.
7) When returning the upper electric box cover, be careful not to pinch the fan motor lead wire.
Top plate
Upper electric
box cover
Notch
PCB
Lower electric
box cover
1) Remove the
two screws.
2) Remove the
one screw.
4) Remove the lower
electric box cover.
3) Remove the upper
electric box cover
from the hook.
J3
J4
J5
PCB
5) Cut jumper J4.
Hook
Fan motor lead wire
Electric box
Содержание
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Low voltage 2006 95 ec machinery 2006 42 ec electromagnetic compatibility 2004 108 ec 2
- P291651 7d_offset book page 1 sunday july 8 2012 3 14 pm 2
- P327445 5a 2
- Rxl42j3v1b 2
- Takayuki fujii managing director 1st of 012 2
- Caution 3
- N english 1 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- N english 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- N english 3 5
- Outdoor unit installation drawings 5
- Installation guidelines 6
- Installing outdoor unit 6
- N english 6
- Outdoor unit installation 6
- Precautions on installation 6
- Caution 7
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- N english 8
- Purging air and checking gas leakage 8
- Warning 8
- Important information regarding the refrigerant used 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- Caution 10
- How to force cooling operation mode 10
- N english 10
- Pump down operation 10
- Caution 11
- Facility setting cooling at low outdoor temperature 11
- N english 9 11
- Caution 12
- Good wrong 12
- N english 12
- Warning 12
- Wiring 12
- C74 c75 c94 13
- C95 capacitor 13
- Db1 db2 db3 diode bridge 13
- E1h heater 13
- English 13
- Fu1 fu2 fu3 13
- Fu4 fu5 fuse 13
- Fu6 field fuse 13
- Ipm1 intelligent power module 13
- L live 13
- L1 coil 13
- L1r reactor 13
- M1c compressor motor 13
- M1f fan motor 13
- Mrcw mrm10 13
- Mrm20 mr30 magnetic relay 13
- N english 11 13
- N neutral 13
- Pcb1 printed circuit board 13
- Protective earth 13
- Q1di earth leak detector 13
- Q1l overload protector 13
- Q31 igbt 13
- R1t r3t thermistor 13
- S1t thermostat 13
- S20 s40 s70 13
- S80 s90 13
- Sa1 surge arrester 13
- V1 v3 v4 varistor 13
- Wiring diagram 13
- Wiring diagram parts table 13
- X11a s1 connector 13
- X1m terminal strip 13
- Y1e electronic expansion valve coil 13
- Y1r reversing solenoid valve coil 13
- Z1c z2c z3c 13
- Z4c ferrite core 13
- N english 14
- Test items 14
- Test run and final check 14
- Trial operation and testing 14
Похожие устройства
- Daikin RXS60F2V1B Руководство по монтажу
- Daikin RXS60F3V1B Руководство по монтажу
- Daikin RXS60F4V1B Руководство по монтажу
- Daikin RXS71FAV1B Руководство по монтажу
- Daikin RXS71FV1B Руководство по монтажу
- Daikin RXS71FAV1B9 Руководство по монтажу
- Daikin RXS71FAV1B8 Руководство по монтажу
- Daikin RKS71FAV1B Руководство по монтажу
- Daikin RKS71FV1B Руководство по монтажу
- Daikin RXM42R2V1B Руководство по монтажу
- Daikin RXM50R2V1B Руководство по монтажу
- Daikin RXM60R2V1B Руководство по монтажу
- Daikin RXM71R2V1B Руководство по монтажу
- Daikin RXS50J2V1B Руководство по монтажу
- Daikin RKS50J2V1B Руководство по монтажу
- Daikin RKS60F3V1B Руководство по монтажу
- Daikin RXS50G2V1B Руководство по монтажу
- Daikin RKS50G2V1B Руководство по монтажу
- Daikin RKS60F2V1B Руководство по монтажу
- Daikin RYN50E3V1B Руководство по монтажу