Daikin FFQ60B8V1B [10/14] Field setting

Daikin FFQ60B8V1B [10/14] Field setting
Installation manual
7
FFQ25~60B8V1B
Split System air conditioners
4PW23700-1B
FIELD SETTING
Field setting must be made from the remote controller in accordance
with the installation condition.
Setting can be made by changing the "Mode number", "FIRST
CODE No." and "SECOND CODE No.".
For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.
Setting air discharge direction
For changing air discharge direction (2 or 3 directions), refer to the
option handbook of the optional blocking pad kit. (SECOND CODE
No. is factory set to "01" for air discharge in 4 directions.)
Settings for options
For settings of options, see the installation instructions provided with
the option.
Setting air filter sign
Remote controllers are equipped with liquid crystal air filter signs to
display the time to clean the air filter.
Change the SECOND CODE No. Depending on the amount of dirt or
dust in the room. (SECOND CODE No. is factory set to "01" for air
filter contamination-light)
Air Filter contamination
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
Main/sub changeover
1 Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 13)
(The remote controller PC board is attached to the upper part of
the remote controller.)
2 Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 16)
(Leave the switch of the other remote controller set to "M".)
INSTALLATION OF THE DECORATION PANEL
Read the chapter "Test operation" on page 7 before making a test run
without attaching the decoration panel.
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop. (See figure 15)
TEST OPERATION
Make sure the control box lids are closed on the indoor and outdoor units.
Refer to "For the following items, take special care during
construction and check after installation is finished" on page 2.
After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.
TEST OPERATION AFTER INSTALLING DECORATION PANEL
1 Open the gas side stop valve.
2 Open the liquid side stop valve.
3 Electrify crank case heater for 6 hours.
4 Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.
5 Press Inspection/Test Operation button 4 times (2 times for
wireless remote controller) and operate at Test Operation mode
for 3 minutes.
6 Push air flow direction adjust button to make sure the unit is in
operation.
7 Press Inspection/Test Operation button and operate normally.
8 Confirm function of unit according to the operation manual.
TEST OPERATION BEFORE INSTALLING DECORATION PANEL
(See NOTE 3. on page 8)
1 Open the gas side stop valve.
2 Open the liquid side stop valve.
3 Electrify crank case heater for 6 hours.
4 Set to cooling operation with the wired remote controller and
start operation by pushing ON/OFF button. "A7" appears on the
display.
5 Press Inspection/Test Operation button on the remote controller
and operate at Test Operation mode for 3 minutes.
6 Press Inspection/Test Operation button and operate normally.
7 Confirm function of unit according to the operation manual.
8 Turn off the main power supply after operation.
PRECAUTIONS
1 Refer to the installation manual attached to the outdoor unit in
case of Individual Operation System type.
2 Conduct test operation after installing decoration panel if the
wireless remote controller is used.
Setting
Display
interval
Mode n° 1st code n° 2nd code n°
Light ±2500 hrs 10 (20) 0 01
Heavy ±1250 hrs 10 (20) 0 02
1 Remote controller PC board
2 Factory setting
3 Only one remote controller needs to be changed