Daikin FTKS60EV1B [55/258] Discharge pipe temperature control

Daikin RN50E2V1B [55/258] Discharge pipe temperature control
Control Specification SiBE04-609
46 Function and Control
3.3.4 3 Minutes Stand-by
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
3.4 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
85
70
55
Zone Control contents
Stop zone When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone Start the timer, and the frequency will be drooping.
Keep zone Keep the upper limit of frequency.
Reset zone Cancel the upper limit of frequency.
A˚C
B˚C
C˚C
D˚C
E˚C
(R5205)
A
B
C
D
E
50/60 class
110
103
102
101
95
71 class
120
111
109
107
107
Keep zone
Stop zone
Reset zone
Discharge pipe
temperature
Drooping
zone