Si04-703A Troubleshooting
Service Diagnosis 119
Troubleshooting
Check No.06
Refer to P.132
P4
: Radiation fin thermistor
J3
: Discharge pipe thermistor
J6
: Outdoor heat exchanger thermistor
H9
: Outdoor air thermistor
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(R7346)
NO
YES
YES
YES
NO
NO
NO
YES
Turn on the power again.
Normal?
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
z Radiation fin thermistor
z Discharge pipe thermistor
z Outdoor heat exchanger
thermistor
z Outdoor air thermistor
z Indoor heat exchanger
thermistor
Replace the following
thermistor.
Replace the outdoor unit
PCB.
(Replace the indoor unit
PCB.)
Connector or thermistor
disconnected?
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 06
Check the thermistor resistance
value.
Check No. 06
Check the indoor heat exchanger
thermistor resistance value in the
heating mode.