Daikin FHQ125BUV1B [284/340] Removal of propeller fan and fan motor

Daikin FHQ35BUV1B [284/340] Removal of propeller fan and fan motor
Si21-205A Outdoor Unit (25/35 class)
Removal Procedure 273
3.4 Removal of Propeller Fan and Fan Motor
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work
.
Step Procedure Points
1. Disconnect the fan motor
connector S70.
Remove the external plates
and the drip proof cover
protecting the electric parts.
Be sure to avoid forgetting to
restore the shelter and to
avoid losing or damaging it.
When restoring, match the
mark of the propeller fan with
the D-cut of the motor shaft.
The fan should be restored
so that the mark
will be at
upper part of the fan motor.
1
Release the lead-wires
of the fan motor from
the groove of the
switch box.
2
The propeller fan can
be removed when the
washer faced nut (M8)
is removed.
3
Remove two screws for
removing the fan
motor. The lead wires
are disengaged by
raising the hooks which
fix the lead wires.

Содержание