Daikin FHQ125BUV1B [51/340] Wiring example for ffq model

Daikin FHQ100BUV1B [51/340] Wiring example for ffq model
Field Piping and Wiring Si21-205A
40 Field Piping and Wiring
1.2.3 Wiring Example For FFQ Model
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
Pair type
:
1 remote controller controls 1 indoor unit. (standard system) (Refer to Fig. 25)
Multi system
:
1 through 4 indoor units connect to 1 outdoor unit. The indoor unit is
controlled by remote controller connected to each indoor unit. (Refer to Fig. 26)
However, the group control is not expected.
Group control
:
1 remote controller controls up to 16 indoor units. (All indoor units operate
according to the remote controller) (Refer to Fig. 27)
2 remote controllers control
:
2 remote controllers control 1 indoor unit. (Refer to Fig. 28)
Note: 1. All transmission wiring except for the remote controller wires is polarized and must match
the terminal symbol.
2. In case a shielding wire is to be used, connect a shielded portion with the of a remote
controller terminal board.(Also, connect the ground for the remote control to a grounded
metal part.)
3. For group control remote controller, choose the remote controller that suits the indoor unit
which has the most functions (as attached swing flap)
Pair type
Multi system
Main power supply
Main switch
123
1
PP
23
1
P1
2
P2
Fuse
Outdoor unit
Indoor unit
Group control
Main power supply
Main switch
123
1
PP
23
1
P1
2
P2
Fuse
Outdoor unit
Main power supply
Main switch
123
1
PP
23
12
Fuse
Outdoor unit
Main power supply
Main switch
123
1
PP
23
12
Fuse
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Fig. 25
Fig. 27
Fig. 28
Fig. 26
Remote
controller 2
(Optional
accessories)
Remote
controller 1
(Optional
accessories)
Remote controller
(Optional accessories)
Remote controller
(Optional accessories)
2 remote controllers control
Main power supply
Main switch
123
1
PP
23
1
P1
2
P2
P1
P2
Fuse
Outdoor unit
Indoor unit
Main power supply
Main switch
123
123
PP12
PP12
123
123
PP12
PP12
123
123
PP12
PP12
Fuse
Outdoor unit
Indoor
unit
Indoor
unit
Indoor
unit
Remote controller
(Optional accessories)

Содержание

Скачать