Si21-205A Field Piping and Wiring
Field Piping and Wiring 41
1.2.4 Electric Wiring Work For FFQ Model
All field supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also
Wiring diagram label
attached to the Control box lid.
For remote controller wiring details, refer to the installation manual attached to the remote
controller.
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the entire system must be
installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply
electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch, and
wiring instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground
wires.
Gas pipes
:
might cause explosions or fire if gas leaks.
Water pipes : no grounding effect if hard vinyl piping is used.
Telepone ground wires or lightning rods : might cause abnormally high electric potential
in the ground during lighting storms.
Specifications for field wire
Table 4
*This will be the total extended length in the system when doing group control.
Note: 1. Shows only in case of protected pipes. Use H07RN-F in case of no protection.
2. For European and Asian market : Vinyl cord with sheath or cable (Insulated thickness : 1mm
or more) For Australian regular
:
Shield wire (Insulated thickness
:
1mm or more)
Caution
Arrange the wires and fix a lid firmly so that the lid does not float during wiring work.
Do not clamp remote controller cords together with wiring between units together. Doing so
may cause malfunction.
Remote controller cords and wiring between units should be located at least 50 mm from
other electric wires. Not following this guideline may result in malfunction due to electrical
noise.
Wire Size(mm
2
)
Total Length
Wiring between units H05VV-U4G(NOTE 1) 2.5
Max.200m
Remote controller cord
Vinyl cord with sheath or cable (2 wire)
(NOTE 2)
0.75-1.25
Max.500m *
Wiring to ground terminal Ground wire conform to local codes 2.0