Daikin FHQ125BUV1B Сервис мануал онлайн [42/340] 600849

Daikin FHQ100BUV1B Сервис мануал онлайн [42/340] 600848
Si21-205A Field Piping and Wiring
Field Piping and Wiring 31
2. Torque wrench
Specifications
2 Dimension B Unit:mm
No change in tightening torque
No change in pipes of other sizes
Differences
2 Change of dimension B
Only 1/2", 5/8" are extended
3. Vacuum pump with check valve
Specifications
2 Discharge speed
Maximum degree of vacuum
50 l/min (50Hz) 100.7 kPa ( 5 Torr 755 mmHg)
60 l/min (60Hz)
2 Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adapter
Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
Nominal size Class-1 Class-2 Previous
1/2 24
26 24
5/8 27
29 27
Dimension B
For class-1: R407C
For class-2: R410A
Vacuum pump adapter
Reverse flow preventive
vacuum adapter