Daikin FTKD35DV2Z [145/226] Outdoor unit fan system check

Daikin FTXD35DVMA [145/226] Outdoor unit fan system check
Check Si04-803
134 Service Diagnosis
5.1.7 Outdoor Unit Fan System Check
Check No.09 DC motor
5.1.8 Power Supply Waveforms Check
Check No.10 Measure the power supply waveform between pins 1 and 2 on the terminal board, and check
the waveform disturbance.
Check to see if the power supply waveform is a sine wave (Fig.1).
Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2)
5.1.9 Inverter Units Refrigerant System Check
Check No.11
(R7159)
YES
YES
NO
NO
Outdoor unit fan system
functioning.
Check the outdoor unit fan system.
Go to Check No. 15.
Outdoor unit fan running?
Fan motor
lead wire connector
disconnected?
Reconnect.
[Fig.1] [Fig.2]
Refrigerant system check
Check for gas leaks.
See the section on insufficient gas
detection.
(R8349)
YES
NO
Correct the problem.
Replace the refrigerant.
Is
the discharge
thermistor disconnected
from the holder?