Daikin FCQH140D8VEB [6/25] Specifications

Daikin FCQH100D8VEB [6/25] Specifications
Indoor Units • Cooling Only/Heat Pump • FCQH-D8VEB
Split Sky Air • Indoor Units
4
2 Specifications
3 Safety device settings
Safety devices Item Installation and operation manual
Drain hose
Clamp for drain hose
Washer for hanger bracket
Screws
Installation guide
Insulation for fitting
Sealing pad
Drain sealing pad
Notes The sound power level is an absolute value indicating the power which a sound source generates.
The BYCQ140CW1W has white insulations. Be informed that formation of dirt on white insulations is more visible and that it is
consequently not advised to install the BYCQ140W1W decoration panel in environments exposed to concentrations of dirt.
2-2 Electrical Specifications FCQH71D8VEB FCQH100D8VEB FCQH125D8VEB FCQH140D8VEB
Power Supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
2-1 Technical Specifications FCQH71D8VEB FCQH100D8VEB FCQH125D8VEB FCQH140D8VEB
Safety devices
71 100 125 140
FCQH
PC board fuse 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse °C --- --- --- ---
Fan motor thermal protector °C
Off: 108
±
5
(On: 96
±1
5
)
Off: 108
±
5
(On: 96
±
15
)
Off: 108
±
5
(On: 96
±1
5
)
Off: 108
±
5
(On: 96
±1
5
)
Drain pump fuse °C 145 145 145 145
3TW28921-3
FCQH71-140D8

Содержание