Daikin FHYC35B7V1 [112/344] Evl liquid pipe motorized valve opening restriction evl liquid pipe motorized valve

Daikin CDX60JV1NB [112/344] Evl liquid pipe motorized valve opening restriction evl liquid pipe motorized valve
SiE18-201 System control
Main Functions 101
3. EVL (liquid pipe motorized valve) opening restriction
EVL (liquid pipe motorized valve)
ELV fully closed during normal heating
operation (after elapsed 30 sec or more)
Other than the condition mentioned left
EVLMAX : 100 pulses
EVLMIN : 52 pulses
0 pulse
(M1042)
0 pulse
EVLMAX : 450 pulses
EVLMIN + EVLDP
(10)
EVLMIN : 12 pulses
Closed condition
(M1043)